Siemens 4EU3632-0CK00-0BA0 — Line/Load Reactors

Siemens 4EU3632-0CK00-0BA0 Filter Choke, 810A 800V 15µH

MPN4EU3632-0CK00-0BA0

Siemens Filterdrossel (filter choke) 4EU3632-0CK00-0BA0, rated 810 A AC, 800 V, 15 µH, 30 Hz fundamental, IP00 open-frame, class H insulation.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3632-0CK00-0BA0 — Inductance & Impedance
ParameterValue
Rated inductance0.000015H
4EU3632-0CK00-0BA0 — Identification
ParameterValue
Product designationFilterdrossel
4EU3632-0CK00-0BA0 — Electrical
ParameterValue
Rated operating voltage800V
Number of phases3
Voltage typeAC
Rated operating frequency30Hz
4EU3632-0CK00-0BA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)370W
Power loss, iron core (W)30W
Rated ambient temperature40°C
4EU3632-0CK00-0BA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3632-0CK00-0BA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.321m
Width0.35m
Depth0.237m

Product details

The Siemens 4EU3632-0CK00-0BA0 is a Filterdrossel — a three-phase AC line filter choke rated for 810 A continuous at 800 V, with a nominal inductance of 15 µH. It sits on the line side of a drive or inverter to smooth current ripple and limit harmonic content, sized for a 30 Hz fundamental operating frequency. The IP00 open-frame construction means it mounts inside a cabinet, not on a panel surface; plan for a dedicated enclosure bay with forced air or natural convection to handle the combined 400 W power loss (370 W coil + 30 W iron core).

The 810 A rated current at 800 V AC tells you this choke is built for a high-power drive — think 600–700 kW motor loads on a 690 V line. The 15 µH inductance at 30 Hz fundamental is a low-value design, typical for drives that switch at higher carrier frequencies (2–16 kHz) where the choke mainly attenuates switching ripple rather than 50/60 Hz harmonics. The 30 Hz fundamental rating means it's optimized for variable-frequency drives running below 30 Hz output; if your application runs above 30 Hz, check the saturation curve — the core may saturate at higher frequencies. Class H insulation (180 °C rated) gives headroom for the 40 °C ambient and the 370 W coil loss; still, derate if ambient exceeds 40 °C or if the enclosure restricts airflow.

Physical fit and connection

Dimensions are 0.35 m wide × 0.321 m tall × 0.237 m deep — a substantial block, roughly 14 × 13 × 9.3 inches. The main current circuit uses flat connectors (bus-bar style), so you'll need copper bars or braided straps rated for 810 A, not lugged cable. No DIN-rail clip; this choke bolts directly to a backplate or chassis. IP00 means no ingress protection — keep it inside a clean, dry cabinet away from washdown or dust.

Frequently asked questions

How do I get current pricing and availability for 4EU3632-0CK00-0BA0?

This part is sourced and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time through our independent distribution network.

What are the key specifications of 4EU3632-0CK00-0BA0?

Rated 810 A AC at 800 V, 15 µH inductance, 30 Hz fundamental frequency, IP00 open-frame, class H insulation, 400 W total power loss (370 W coil + 30 W iron core). Dimensions: 0.35 m wide × 0.321 m tall × 0.237 m deep.

MPN
4EU3632-0CK00-0BA0