Siemens 4EU3652-0UB00-1BA0 — Line/Load Reactors

Siemens 4EU3652-0UB00-1BA0 Mains Choke, 910A, 400/480V AC

MPN4EU3652-0UB00-1BA0

Siemens 4EU3652-0UB00-1BA0, Netzdrossel f. FU, 3-phase AC mains choke, 910A max, 400/480V, IP00, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3652-0UB00-1BA0 — Inductance & Impedance
ParameterValue
Rated inductance0.000015H
Relative inductive voltage drop2%
4EU3652-0UB00-1BA0 — Identification
ParameterValue
Product designationNetzdrossel f. FU
4EU3652-0UB00-1BA0 — Electrical
ParameterValue
Rated operating voltage400, 480V
Rated current (AC)819A
Number of phases3
Current (AC), max.910A
Voltage typeAC
Rated operating frequency50 ... 60Hz
4EU3652-0UB00-1BA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)394W
Power loss, iron core (W)150W
Rated ambient temperature40°C
4EU3652-0UB00-1BA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3652-0UB00-1BA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.321m
Width0.35m
Depth0.237m

Product details

The Siemens 4EU3652-0UB00-1BA0 is a 3-phase AC mains choke (Netzdrossel f. FU) designed for frequency converter input lines. It handles a maximum AC current of 910 A at 400/480 V, 50/60 Hz, making it sized for large variable-frequency drive installations in industrial motor control panels.

Sizing and thermal class

Total power loss breaks into 394 W in the coil and 150 W in the iron core at rated conditions — roughly 544 W of heat to vent from the panel. The IP00 enclosure means it's an open-frame component; install where airflow or forced ventilation can clear that thermal load.

Integration and connections

Dimensions are 0.35 m wide, 0.321 m tall, 0.237 m deep — a substantial footprint that needs a dedicated mounting plate or chassis rail, not a standard DIN rail. Main circuit connections use flat-type terminals (bus-bar or large-lug compatible), typical for high-current power distribution. Inductance is 15 µH (0.000015 H), which combined with the 2% voltage drop gives the line impedance needed for a drive input filter stage. Verify the drive manufacturer's recommended line choke impedance before specifying — this is a fixed-value choke, not adjustable.

Frequently asked questions

How do I get current pricing and availability for 4EU3652-0UB00-1BA0?

This part is sourced and quoted to order against an RFQ through our independent distribution network. Submit an RFQ for current pricing and availability — lead times and firm pricing are confirmed at quote time.

What are the key ratings for 4EU3652-0UB00-1BA0?

Key ratings: 3-phase AC, 910 A maximum current at 400/480 V, 50/60 Hz, 819 A operational current at 40 °C, 15 µH inductance, 2% voltage drop, IP00, thermal class H.

What compliance documentation does this part carry?

It is UL/CSA recognized per EN 61558-2-20, and the IP00 protection class indicates open-frame construction. RoHS and REACH compliance documentation is typically available from the manufacturer upon request.

MPN