Siemens 4EU3652-2UB00-1BA0 — Line/Load Reactors

Siemens 4EU3652-2UB00-1BA0 Mains Choke, 1000A Max, 900A Rate

MPN4EU3652-2UB00-1BA0

Siemens 4EU3652-2UB00-1BA0 mains choke, 3-phase AC, 500V, 1000A max / 900A rated, 2% voltage drop, IP00, thermal class H, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3652-2UB00-1BA0 — Inductance & Impedance
ParameterValue
Rated inductance0.000018H
Relative inductive voltage drop2%
4EU3652-2UB00-1BA0 — Identification
ParameterValue
Product designationNetzdrossel f. FU
4EU3652-2UB00-1BA0 — Electrical
ParameterValue
Rated operating voltage500, 500V
Number of phases3
Voltage typeAC
Rated operating frequency60 ... 50Hz
4EU3652-2UB00-1BA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)310W
Power loss, iron core (W)150W
Rated ambient temperature40°C
4EU3652-2UB00-1BA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3652-2UB00-1BA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.321m
Width0.35m
Depth0.237m

Product details

The Siemens 4EU3652-2UB00-1BA0 is a three-phase mains choke (line reactor) designed for use with frequency converters. It handles a maximum current of 1 000 A and a rated continuous current of 900 A at 500 V AC, with a rated inductance of 0.000018 H (18 µH). Rated for 50/60 Hz operation, the choke is built to thermal class H (180 °C insulation system per IEC 60085), with a total power loss of 460 W (310 W in the coil plus 150 W in the iron core) at the 40 °C ambient rating. The IP00 enclosure means it's an open-frame component intended for installation inside a panel or cabinet — not for standalone outdoor or washdown use.

The 4EU3652-2UB00-1BA0 carries a mature lifecycle stage — it remains available through independent distribution channels, not a current-production factory order. No official successor order code is listed, so for a BOM line this remains the direct fit.

The choke measures 0.35 m wide by 0.321 m tall by 0.237 m deep. Main circuit connections are via flat-type terminals — expect busbar or large cable lugs. The IP00 frame requires mounting inside a ventilated enclosure with clearance for heat dissipation; the 460 W total loss at full load means forced airflow or generous cabinet sizing is advisable.

Frequently asked questions

Where can I buy 4EU3652-2UB00-1BA0?

This part is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What are the key electrical ratings of 4EU3652-2UB00-1BA0?

It is a 3-phase AC mains choke rated at 500 V, with a maximum current of 1 000 A and a rated continuous current of 900 A. The inductance is 0.000018 H (18 µH) with a 2% voltage drop at rated conditions. Operating frequency is 50/60 Hz.

What is the physical size of 4EU3652-2UB00-1BA0?

Dimensions are 0.35 m wide, 0.321 m tall, and 0.237 m deep. It uses flat-type terminals for the main circuit connections.