Skip to main content
Siemens 4EU3652-5UC00-0AA0 — Line/Load Reactors

Siemens 4EU3652-5UC00-0AA0 Mains Choke, 450A, 3-Phase, IP00

MPN4EU3652-5UC00-0AA0

Siemens SIRIUS Netzdrossel f. FU mains choke, 3-phase, 450A rated, 500A max, 400/480V AC, 50-60Hz, IP00, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3652-5UC00-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.000056H
Relative inductive voltage drop4%
4EU3652-5UC00-0AA0 — Identification
ParameterValue
Product designationNetzdrossel f. FU
4EU3652-5UC00-0AA0 — Electrical
ParameterValue
Rated operating voltage400, 480V
Number of phases3
Voltage typeAC
Rated operating frequency50 ... 60Hz
4EU3652-5UC00-0AA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)287W
Power loss, iron core (W)170W
Rated ambient temperature40°C
4EU3652-5UC00-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3652-5UC00-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.321m
Width0.35m
Depth0.237m

Product details

Mains choke for variable-frequency drives

The Siemens 4EU3652-5UC00-0AA0 is a three-phase mains choke (Netzdrossel f. FU) designed to sit between the supply and a variable-frequency drive, smoothing line harmonics and limiting inrush current. Rated at 450 A continuous with a 500 A maximum, it handles the full motor current of large drives on 400 V or 480 V AC lines at 50/60 Hz.

The 450 A rated current and 500 A maximum tell you this choke is sized for a drive with a nominal input current around 450 A — typically a 250–315 kW drive on 400 V, or a 355–400 kW drive on 480 V, depending on the drive's power factor and efficiency. The 0.000056 H inductance (56 µH) at 50/60 Hz is the value that produces the 4 % voltage drop; if your drive manufacturer specifies a different impedance (e.g., 3 % or 5 %), this choke won't match. The IP00 enclosure means it's open-frame — mount inside a cabinet with proper clearance; no washdown or outdoor use. Thermal class H (180 °C insulation) gives headroom for the 287 W coil loss plus 170 W iron loss at rated load.

Physical integration

Dimensions: 0.35 m wide, 0.321 m tall, 0.237 m deep. That's a substantial footprint — about the size of a small suitcase. The flat-type terminals for the main circuit accept busbar or large cable lugs; plan for at least M10 or 3/8" bolt connections. IP00 means no finger-safe enclosure — the choke must be mounted inside a locked or tool-accessible cabinet with clearance to adjacent metalwork for cooling.

Frequently asked questions

How do I get current pricing and availability for 4EU3652-5UC00-0AA0?

Submit an RFQ through this listing; the part is sourced to order through independent distribution, and availability plus current pricing are confirmed at quote time.

Will 4EU3652-5UC00-0AA0 drop into a panel specified around 3RV6011-0CA10 without rewiring?

No — the 3RV6011-0CA10 is a motor-protective circuit breaker (SIRIUS S00, 0.25 A, DIN-rail mount), completely different function and form factor. The 4EU3652-5UC00-0AA0 is a 450 A mains choke with flat-type terminals, requiring busbar connections and cabinet mounting. No direct interchange.

What compliance documentation does this brand provide for 4EU3652-5UC00-0AA0?

The part is UL/CSA-recognized per EN 61558-2-20 as stated in the description. Standard Siemens documentation includes the declaration of conformity for the Low Voltage Directive and RoHS; REACH and IEC compliance data are available on request.