Skip to main content
Siemens 4EU3652-5UC08-0AA0 — Line/Load Reactors

Siemens 4EU3652-5UC08-0AA0 Mains Choke, 450A, 3-Phase, 400/4

MPN4EU3652-5UC08-0AA0

Siemens 4EU3652-5UC08-0AA0 mains choke (Netzdrossel f. FU), 3-phase AC, 450A rated current, 500A max, 400/480V, 50-60Hz, IP20, thermal class H, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3652-5UC08-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.000056H
Relative inductive voltage drop4%
4EU3652-5UC08-0AA0 — Identification
ParameterValue
Product designationNetzdrossel f. FU
4EU3652-5UC08-0AA0 — Electrical
ParameterValue
Rated operating voltage400, 480V
Number of phases3
Voltage typeAC
Rated operating frequency50 ... 60Hz
4EU3652-5UC08-0AA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)287W
Power loss, iron core (W)170W
Rated ambient temperature40°C
4EU3652-5UC08-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3652-5UC08-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP20
Height0.321m
Width0.35m
Depth0.237m

Product details

The Siemens 4EU3652-5UC08-0AA0 is a three-phase mains choke (Netzdrossel f. FU) rated for 450 A continuous with a maximum of 500 A, designed for line-side installation ahead of a frequency converter. It operates on 400/480 V AC at 50 to 60 Hz and delivers a relative inductive voltage drop of 4% at rated current — the figure that governs how much harmonic attenuation and voltage sag the choke introduces into the drive's input circuit.

The 450 A rated current (500 A maximum) sets the continuous load capacity for a 3-phase AC line feeding a variable-frequency drive. The 4% inductive voltage drop is the key selection parameter: it tells you the choke's impedance at line frequency, which determines its effectiveness at reducing harmonic distortion and limiting inrush current. At 40 °C ambient, the total power loss splits between the coil (287 W) and the iron core (170 W) — thermal class H insulation per IEC 60085 means the winding can tolerate sustained temperatures up to 180 °C, so the choke can be mounted in a warm cabinet without derating as long as airflow is adequate.

Integration notes

Dimensions are 0.35 m wide by 0.321 m tall by 0.237 m deep — a substantial footprint that requires panel layout planning. The main circuit connection uses flat-type terminals (flat connector), so the mating bus bars or cable lugs must be compatible with that interface. Inductance is 0.000056 H (56 µH) at rated conditions.

Frequently asked questions

How do I get current pricing and availability for 4EU3652-5UC08-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ to receive current pricing and availability confirmation at quote time.

What is the depth of 4EU3652-5UC08-0AA0?

The listed depth is 0.237 m (237 mm).

What is the width of 4EU3652-5UC08-0AA0?

The listed width is 0.35 m (350 mm).

MPN