Siemens 4EU3652-7UB00-1BA0 — Line/Load Reactors

Siemens 4EU3652-7UB00-1BA0 Line Reactor, 450A, 3-Phase

MPN4EU3652-7UB00-1BA0

Siemens SENTRON 4EU3652-7UB00-1BA0 mains choke for variable-frequency drives, 3-phase, 500V AC, 450A rated, 500A max, 50 Hz, IP00, flat-type terminals.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EU3652-7UB00-1BA0 — Inductance & Impedance
ParameterValue
Rated inductance0.000073H
Relative inductive voltage drop4%

Identification

4EU3652-7UB00-1BA0 — Identification
ParameterValue
Product designationNetzdrossel f. FU

Electrical

4EU3652-7UB00-1BA0 — Electrical
ParameterValue
Rated operating voltage500V
Number of phases3
Voltage typeAC
Rated operating frequency50Hz

Losses & Thermal

4EU3652-7UB00-1BA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)300W
Power loss, iron core (W)146W
Rated ambient temperature40°C

Approvals

4EU3652-7UB00-1BA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H

Mechanical

4EU3652-7UB00-1BA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.321m
Width0.35m
Depth0.237m

Product details

Line Reactor for Variable-Frequency Drives

The Siemens 4EU3652-7UB00-1BA0 is a three-phase mains choke (Netzdrossel f. FU) designed for the input of variable-frequency drives. It is rated for 450 A continuous (500 A maximum) at 500 V AC, 50 Hz, with an inductance of 0.073 mH and a relative inductive voltage drop of 4% at rated current. The 4% voltage drop at rated current is the key selection parameter: it limits harmonic distortion and reduces peak currents on the drive input, but the voltage drop subtracts from the available DC bus voltage. For a drive running near its voltage ceiling, the 4% drop may limit output voltage — confirm the drive's minimum bus voltage requirement before specifying. Class H insulation (per IEC 60085) means the winding can sustain 180°C hot-spot temperature — necessary for a reactor dissipating 446 W total (300 W coil loss + 146 W iron core loss) at 40°C ambient. Mount with free air circulation around the 0.35 m × 0.321 m × 0.237 m enclosure; IP00 means no dust or moisture protection, so it belongs in a clean, dry cabinet — not on the factory floor.

Lifecycle and Sourcing

UL and CSA recognition per EN 61558-2-20 is confirmed on the nameplate. The standard covers safety requirements for chokes and reactors; UL/CSA listing means the part is accepted for North American panel builds without additional agency review.

Integration Notes

Flat-type terminals on the main current circuit accept bus bar or large cable lugs — no screw-clamp or spring-cage connection. Plan for bolted connections with appropriate torque tooling. The 0.35 m width and 0.321 m height mean it occupies roughly the footprint of a small suitcase; panel layout must allow clearance for the IP00 enclosure and airflow around all sides.

Frequently asked questions

Where can I buy the 4EU3652-7UB00-1BA0?

This part is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

What are the key electrical ratings of this mains choke?

Rated 450 A continuous, 500 A maximum, 500 V AC, 50 Hz, 3-phase, 0.073 mH inductance, 4% voltage drop at rated current. Total power loss 446 W at 40°C ambient.

What compliance documentation comes with this part?

UL and CSA recognized per EN 61558-2-20. Class H insulation per IEC 60085. RoHS and REACH compliance documentation is standard with Siemens industrial products; request with the RFQ.

MPN