Skip to main content
Siemens 4EU3652-7UC00-1BA0 — Line/Load Reactors

Siemens 4EU3652-7UC00-1BA0 Mains Choke, 1120 A, 400/480 V AC

MPN4EU3652-7UC00-1BA0

Siemens 4EU3652-7UC00-1BA0 mains choke for variable-frequency drives, 3-phase, AC 400/480 V, 1120 A max, 50/60 Hz, IP00, flat-type terminals, UL/CSA recognized, EN 61558-2-20.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EU3652-7UC00-1BA0 — Inductance & Impedance
ParameterValue
Rated inductance0.000012H
Relative inductive voltage drop2%

Identification

4EU3652-7UC00-1BA0 — Identification
ParameterValue
Product designationNetzdrossel f. FU

Electrical

4EU3652-7UC00-1BA0 — Electrical
ParameterValue
Rated operating voltage400, 480V
Rated current (AC)1 008A
Number of phases3
Current (AC), max.1 120A
Voltage typeAC
Rated operating frequency50 ... 60Hz

Losses & Thermal

4EU3652-7UC00-1BA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)394W
Power loss, iron core (W)135W
Rated ambient temperature40°C

Approvals

4EU3652-7UC00-1BA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H

Mechanical

4EU3652-7UC00-1BA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.321m
Width0.35m
Depth0.237m

Product details

Mains choke for VFD line input — 1120 A, 400/480 V AC

The Siemens 4EU3652-7UC00-1BA0 is a three-phase mains choke (Netzdrossel f. FU) sized for variable-frequency drive input lines. It carries a maximum AC current of 1120 A at 400/480 V AC, 50/60 Hz, with a rated operational current of 1008 A. The rated inductance is 0.0126 mH (12.6 µH) and the relative inductive voltage drop is 2% at rated current, voltage, and frequency — this limits harmonic distortion and inrush current on the drive's DC link without excessive voltage drop under load. The choke is IP00 — open-frame construction — so it must be installed inside a cabinet with appropriate clearance and ventilation. Thermal class H (IEC 60085) insulation allows continuous operation at 40 °C ambient, with a total power loss of 529 W (394 W coil, 135 W iron core). Connections are via flat-type terminals, sized for the 1120 A circuit. Compliance documentation covers EN 61558-2-20 and UL/CSA recognition, so the part meets the common North American and European safety standards for drive input chokes.

Integration note

At 350 mm wide, 321 mm high, and 237 mm deep, the choke occupies a significant footprint inside the cabinet. IP00 construction means it must be mounted on a non-flammable base with at least 50 mm clearance to adjacent components for airflow. Flat-type terminals require busbar or large-crimp lugs — plan the connection layout before final assembly.

Frequently asked questions

How do I get current pricing and availability for 4EU3652-7UC00-1BA0?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time via our independent distribution network — no automated price or lead-time figure is published.

What compliance documentation does 4EU3652-7UC00-1BA0 carry?

The choke is recognized to UL/CSA standards and complies with EN 61558-2-20 for safety of transformers, reactors, and power supply units.

What are the key dimensions of 4EU3652-7UC00-1BA0?

Width 0.35 m, height 0.321 m, depth 0.237 m. Open-frame IP00 — no enclosure.

MPN
4EU3652-7UC00-1BA0