Skip to main content
Siemens 4EU3652-7UC00-1BA0 — Line/Load Reactors

Siemens 4EU3652-7UC00-1BA0 Mains Choke, 1120 A, 400/480 V AC

MPN4EU3652-7UC00-1BA0

Siemens 4EU3652-7UC00-1BA0 mains choke for variable-frequency drives, 3-phase, AC 400/480 V, 1120 A max, 50/60 Hz, IP00, flat-type terminals, UL/CSA recognized, EN 61558-2-20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

4EU3652-7UC00-1BA0 specifications
ParameterValue
Type of voltageAC
Type of electrical connection for main current circuitflat connector
Operating voltage rated value400, 480V
Relative inductive drop in voltage for rated value of the current, voltage and frequency2%
Current at AC maximum1 120A
Operational current at AC rated value1 008A
Power loss [W] of the coil394W
Power loss [W] of the iron core135W
Operating frequency rated value50 ... 60Hz
Phase number3
Ambient temperature rated value40°C
Depth0.237m
Width0.35m
Height0.321m
Thermal class acc. to IEC 60085H
Protection class IPIP00
Inductivity rated value0.000012H

Product details

Mains choke for VFD line input — 1120 A, 400/480 V AC

The Siemens 4EU3652-7UC00-1BA0 is a three-phase mains choke (Netzdrossel f. FU) sized for variable-frequency drive input lines. It carries a maximum AC current of 1120 A at 400/480 V AC, 50/60 Hz, with a rated operational current of 1008 A. The rated inductance is 0.0126 mH (12.6 µH) and the relative inductive voltage drop is 2% at rated current, voltage, and frequency — this limits harmonic distortion and inrush current on the drive's DC link without excessive voltage drop under load. The choke is IP00 — open-frame construction — so it must be installed inside a cabinet with appropriate clearance and ventilation. Thermal class H (IEC 60085) insulation allows continuous operation at 40 °C ambient, with a total power loss of 529 W (394 W coil, 135 W iron core). Connections are via flat-type terminals, sized for the 1120 A circuit. Compliance documentation covers EN 61558-2-20 and UL/CSA recognition, so the part meets the common North American and European safety standards for drive input chokes.

Integration note

At 350 mm wide, 321 mm high, and 237 mm deep, the choke occupies a significant footprint inside the cabinet. IP00 construction means it must be mounted on a non-flammable base with at least 50 mm clearance to adjacent components for airflow. Flat-type terminals require busbar or large-crimp lugs — plan the connection layout before final assembly.

Frequently asked questions

How do I get current pricing and availability for 4EU3652-7UC00-1BA0?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time via our independent distribution network — no automated price or lead-time figure is published.

What compliance documentation does 4EU3652-7UC00-1BA0 carry?

The choke is recognized to UL/CSA standards and complies with EN 61558-2-20 for safety of transformers, reactors, and power supply units.

What are the key dimensions of 4EU3652-7UC00-1BA0?

Width 0.35 m, height 0.321 m, depth 0.237 m. Open-frame IP00 — no enclosure.

MPN
4EU3652-7UC00-1BA0