Skip to main content
Siemens 4EU3652-8UB00-0AA0 — Line/Load Reactors

Siemens 4EU3652-8UB00-0AA0 Mains Choke, 3-Phase, 690V, 224A

MPN4EU3652-8UB00-0AA0

Siemens 4EU3652-8UB00-0AA0 mains choke (Netzdrossel f. FU), 3-phase, 690V AC, 224A max / 201.6A rated, 0.23mH, 4% voltage drop, IP00, flat-type terminals, thermal class H.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EU3652-8UB00-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.00023H
Relative inductive voltage drop4%

Identification

4EU3652-8UB00-0AA0 — Identification
ParameterValue
Product designationNetzdrossel f. FU

Electrical

4EU3652-8UB00-0AA0 — Electrical
ParameterValue
Rated operating voltage690V
Number of phases3
Voltage typeAC
Rated operating frequency50Hz

Losses & Thermal

4EU3652-8UB00-0AA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)300W
Power loss, iron core (W)138W
Rated ambient temperature40°C

Approvals

4EU3652-8UB00-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H

Mechanical

4EU3652-8UB00-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.321m
Width0.35m
Depth0.237m

Product details

What it is and what it does

The Siemens 4EU3652-8UB00-0AA0 is a three-phase mains choke (Netzdrossel f. FU) designed for installation ahead of a frequency converter. It limits harmonic currents and reduces line-side distortion, protecting both the drive and upstream equipment. Rated for 690 V AC at 50 Hz, it carries a maximum continuous current of 224 A and a rated current of 201.6 A, with an inductance of 0.23 mH and a relative inductive voltage drop of 4% at rated conditions.

Key ratings and what they mean for fit

The 224 A maximum current and 201.6 A rated current define the thermal limit under continuous operation at 40 °C ambient. The 4% voltage drop is the impedance at rated current — a standard value for line reactors that provides effective harmonic attenuation without excessive voltage sag. The 0.23 mH inductance is the actual winding value; paired with the 690 V AC rating, this choke is sized for medium-voltage drive inputs or high-line 480 V systems where the extra headroom is needed. Thermal class H (180 °C) insulation means the winding can tolerate sustained overloads better than class B or F designs — relevant if the drive cycles near the rated current repeatedly.

Deployment context and integration

IP00 means no enclosure — this choke is intended for installation inside a panel or cabinet. The flat-type terminals accept busbar or large cable lugs; plan for a 0.35 m width, 0.321 m height, and 0.237 m depth footprint. Total power loss is 300 W coil plus 138 W iron core, so forced ventilation or generous cabinet volume is needed to keep ambient below the 40 °C rating.

MPN
4EU3652-8UB00-0AA0