Skip to main content
Siemens 4EU3921-0AL00-0A — Line/Load Reactors

4EU3921-0AL00-0A Commutating Choke, 3-Phase 400V 1040A AC, I

MPN4EU3921-0AL00-0A

Siemens 4EU3921-0AL00-0A commutating choke for converter, 3-phase, 400V AC, 1040A max AC current, 22µH inductance, IP00, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3921-0AL00-0A — Inductance & Impedance
ParameterValue
Rated inductance0.000022H
Relative inductive voltage drop4%
4EU3921-0AL00-0A — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU3921-0AL00-0A — Electrical
ParameterValue
Rated operating voltage400V
Rated current (AC)936A
Number of phases3
Current (AC), max.1 040A
Rated current (DC)1 274.5A
Voltage typeAC
Rated operating frequency50Hz
Peak current1 300A
4EU3921-0AL00-0A — Losses & Thermal
ParameterValue
Power loss, coil (W)535W
Power loss, iron core (W)210W
Rated ambient temperature40°C
4EU3921-0AL00-0A — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3921-0AL00-0A — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.385m
Width0.41m
Depth0.229m

Product details

The Siemens 4EU3921-0AL00-0A is a commutating choke (line reactor) designed for use with 3-phase AC converters. It's rated for a 400V AC supply at 50Hz and handles a maximum continuous AC current of 1040A, with a peak current capability of 1300A.

The 1040A AC maximum current rating (Ithmax) is the thermal continuous current limit at 40°C ambient. The operational AC current (ILN) is 936A — that's the current at which the 4% inductive voltage drop is specified. For DC applications, the rated current is 1274.5A. Thermal class H (IEC 60085) means the winding insulation can withstand a 180°C hot-spot temperature, giving good margin in high-ambient or overload conditions. Total power loss is 745W — 535W from the coil and 210W from the iron core — so factor that heat into your enclosure ventilation.

This choke sits between the converter (VFD) and the motor, or on the line side of the converter, to limit di/dt and reduce harmonic distortion. Common in drive systems for pumps, fans, conveyors, and compressors in industrial plants. The flat-type main circuit terminals are designed for busbar connection — not wire lugs — so plan your panel buswork accordingly.

Frequently asked questions

Does 4EU3921-0AL00-0A have UL or CSA approval?

Yes, the product description states it is UL/CSA-recognized and designed per EN 61558-2-20.

MPN
4EU3921-0AL00-0A