Skip to main content
Siemens 4EU3921-0BA00-0A — Line/Load Reactors

Siemens 4EU3921-0BA00-0A Commutating Choke, 405A, 750V AC

MPN4EU3921-0BA00-0A

Siemens 4EU3921-0BA00-0A commutating choke (line reactor) for converter applications, 3-phase, 405A rated / 450A max, 750V AC, 0.12 mH, IP00, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3921-0BA00-0A — Inductance & Impedance
ParameterValue
Rated inductance0.00012H
Relative inductive voltage drop4%
4EU3921-0BA00-0A — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU3921-0BA00-0A — Electrical
ParameterValue
Rated operating voltage750V
Number of phases3
Rated current (DC)551.4A
Voltage typeAC
Rated operating frequency50Hz
4EU3921-0BA00-0A — Losses & Thermal
ParameterValue
Power loss, coil (W)394W
Power loss, iron core (W)288W
Rated ambient temperature40°C
4EU3921-0BA00-0A — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3921-0BA00-0A — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.385m
Width0.41m
Depth0.229m

Product details

Rated 405 A continuous with a 450 A maximum thermal current at 750 V AC, 50 Hz, it carries a 0.12 mH inductance and a 4 % relative inductive voltage drop at rated conditions.

The 405 A rated current (I_LN) and 450 A maximum thermal current (I_thmax) define the continuous load envelope — this choke can carry a 405 A fundamental current indefinitely at 40 °C ambient, with headroom to 450 A for overloads that stay within the thermal time constant. The 750 V AC operating voltage covers 400 V, 480 V, and 690 V line-to-line systems common in European and North American industrial drives. The 0.12 mH inductance and 4 % voltage drop (at rated current and frequency) are the values the drive manufacturer expects to see for proper DC-link ripple filtering and commutation notch suppression; swapping in a choke with a different inductance shifts the notch frequency and may increase peak voltages across the rectifier diodes. The IP00 rating means the choke is an open-frame component — no enclosure, no finger-safe protection. The thermal class H (IEC 60085) insulation system allows a 180 °C hot-spot temperature, which is standard for converter-duty chokes that see both fundamental current and switching-frequency harmonics. The flat-type terminals accept busbar or large cable lugs; plan for a bolted connection, not spring-clamp or screw-cage wiring.

MPN
4EU3921-0BA00-0A