The 480A maximum current and 432A rated current define the continuous thermal capacity at 50°C ambient. For a drive line feeding a 400–480V motor load, this choke sits on the line side of the converter, limiting di/dt and reducing harmonics. The 4.5% voltage drop at rated current is typical for a 3%–5% impedance line reactor — enough to mitigate nuisance tripping on weak mains but not so high it drops significant torque. Physical size: 0.41m wide × 0.385m tall × 0.229m deep. That is a substantial footprint — roughly the size of a small suitcase. Plan for a mounting plate or sub-panel; it does not snap onto a DIN rail.
Siemens 4EU3921-0BF10-0A Commutating Choke, 480A, 600V AC
MPN4EU3921-0BF10-0A
Siemens 4EU3921-0BF10-0A commutating choke for converter, 3-phase, 600V AC, 480A max / 432A rated, 50Hz, 0.104 mH, IP00, flat-type terminal, class H insulation.
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Rated inductance | 0.00011H |
| Relative inductive voltage drop | 4.5% |
| Parameter | Value |
|---|---|
| Product designation | Kommut.-Drossel f. Stromrichter |
| Parameter | Value |
|---|---|
| Rated operating voltage | 600V |
| Number of phases | 3 |
| Rated current (DC) | 588.2A |
| Voltage type | AC |
| Rated operating frequency | 50Hz |
| Parameter | Value |
|---|---|
| Rated ambient temperature | 50°C |
| Parameter | Value |
|---|---|
| Thermal class (IEC 60085) | H |
| Parameter | Value |
|---|---|
| Main-circuit connection type | flat connector |
| IP protection rating | IP00 |
| Height | 0.385m |
| Width | 0.41m |
| Depth | 0.229m |
Product details
Frequently asked questions
Does the 4EU3921-0BF10-0A mount on a DIN rail?
No. It is a panel-mount component with IP00 protection and flat-type terminals. It requires a mounting plate or sub-panel; dimensions are 0.41m wide by 0.385m tall by 0.229m deep.
MPN
4EU3921-0BF10-0A