Skip to main content
Siemens 4EU3921-1AA00-0A — Line/Load Reactors

Siemens 4EU3921-1AA00-0A Commutating Choke, 900A/1000A, 400V

MPN4EU3921-1AA00-0A

Siemens SENTRON 4EU3921-1AA00-0A commutating choke for converter, 3-phase, 400V AC, rated 900A (max 1000A), 27µH, IP00, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3921-1AA00-0A — Inductance & Impedance
ParameterValue
Rated inductance0.000027H
Relative inductive voltage drop4%
4EU3921-1AA00-0A — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU3921-1AA00-0A — Electrical
ParameterValue
Rated operating voltage400V
Number of phases3
Rated current (DC)1 225.4A
Voltage typeAC
Rated operating frequency50Hz
4EU3921-1AA00-0A — Losses & Thermal
ParameterValue
Power loss, coil (W)360W
Power loss, iron core (W)277W
Rated ambient temperature40°C
4EU3921-1AA00-0A — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3921-1AA00-0A — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.385m
Width0.41m
Depth0.229m

Product details

Commutating Choke for Converter Duty — 900 A, 400 V AC, 3-Phase

The Siemens 4EU3921-1AA00-0A is a 3-phase commutating choke (line reactor) designed for converter front ends, rated at 900 A continuous with a maximum of 1 000 A at 400 V AC, 50 Hz. The 27 µH inductance limits di/dt and reduces harmonic distortion on the drive input, with a relative inductive voltage drop of 4 % at rated current — a standard value for line reactors in industrial converter applications.

Power Loss and Thermal Class

Total power loss is 637 W — 360 W in the coil and 277 W in the iron core — at the rated 40 °C ambient. The winding is Class H insulation per IEC 60085, rated for a 180 °C hot-spot temperature, which provides margin in a warm cabinet or near a converter heatsink.

IP00 — Open Construction, Panel Integration

Rated IP00 with no enclosure — this choke is intended for mounting inside a switchgear cubicle or drive cabinet where the enclosure provides the environmental seal. The flat-type terminals accept busbar or lug connections for the main current circuit. Dimensions are 0.41 m wide by 0.385 m tall by 0.229 m deep; plan for adequate clearance around the iron core for airflow and convection cooling.

Lifecycle Status and Sourcing

Frequently asked questions

What are the key ratings of 4EU3921-1AA00-0A?

3-phase commutating choke rated 900 A continuous (max 1 000 A) at 400 V AC, 50 Hz, with 27 µH inductance and a 4 % voltage drop. Total power loss is 637 W at 40 °C ambient, Class H insulation.

Where can I buy 4EU3921-1AA00-0A?

This part is sourced to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time.

Will 4EU3921-1AA00-0A drop into a panel specified around 3RV6011-0CA10?

No — the 3RV6011-0CA10 is a motor-protective circuit breaker (SIRIUS S00, 0.25 A, DIN-rail mount), while the 4EU3921-1AA00-0A is a 900 A converter choke with flat-type terminals and open-frame construction. They serve entirely different functions and panel locations.

MPN