Skip to main content
Siemens 4EU3921-2BA00-0A — Line/Load Reactors

Siemens 4EU3921-2BA00-0A Commutating Choke, 910A AC, 0.025 m

MPN4EU3921-2BA00-0A

Siemens 4EU3921-2BA00-0A commutating choke for converter, 3-phase, 400V AC, 910A AC max, 0.025 mH, IP00, thermal class H, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3921-2BA00-0A — Inductance & Impedance
ParameterValue
Rated inductance0.000025H
Relative inductive voltage drop4%
4EU3921-2BA00-0A — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU3921-2BA00-0A — Electrical
ParameterValue
Rated operating voltage400V
Rated current (AC)819A
Number of phases3
Current (AC), max.910A
Rated current (DC)1 115.1A
Voltage typeAC
Rated operating frequency50Hz
Peak current1 138A
4EU3921-2BA00-0A — Losses & Thermal
ParameterValue
Power loss, coil (W)380W
Power loss, iron core (W)220W
Rated ambient temperature40°C
4EU3921-2BA00-0A — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3921-2BA00-0A — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.385m
Width0.41m
Depth0.229m

Product details

The Siemens 4EU3921-2BA00-0A is a 3-phase commutating choke for converter applications, designed to limit current rise and reduce harmonic distortion on the DC link of a variable-speed drive or rectifier. It's rated for 400V AC at 50 Hz and carries a maximum AC current of 910A, with an operational AC current of 819A and a DC rated current of 1115.1A.

The 910A AC maximum current and 1115.1A DC rated current tell you this choke is sized for a high-power converter — think 400–500 kW drive on a pump, fan, or conveyor in a mill or processing plant. The 0.025 mH inductance is low, meaning it's a line-side choke meant to smooth commutation notches, not a heavy DC-link filter. The 4% voltage drop at rated conditions confirms it's a standard impedance for limiting fault current rise without dropping excessive voltage under load. IP00 protection means it's an open-frame component — no enclosure. The thermal class H insulation (IEC 60085) means the winding can handle a 180°C hot-spot temperature, which gives headroom in a warm panel or when the choke is running near its full 380W coil plus 220W iron-core power loss.

The description explicitly states it is UL/CSA-recognized as a choke.

Frequently asked questions

What is the 4EU3921-2BA00-0A used for?

It is a 3-phase commutating choke for converter applications, used to limit current rise and reduce harmonic distortion on the DC link of variable-speed drives or rectifiers in industrial power systems.

What are the key ratings of 4EU3921-2BA00-0A?

Key ratings: 400V AC, 50 Hz, 910A AC maximum current, 819A AC operational current, 1115.1A DC rated current, 0.025 mH inductance, 4% inductive voltage drop, IP00, thermal class H, 40°C ambient temperature.

Where can I buy 4EU3921-2BA00-0A?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time. Submit an RFQ for a firm price and lead time.

What compliance documentation does 4EU3921-2BA00-0A have?

The choke is designed to EN 61558-2-20 and carries UL/CSA recognition, confirming acceptance in North American and European installations.

MPN