Skip to main content
Siemens 4EU3921-6AA00-0A — Line/Load Reactors

Siemens 4EU3921-6AA00-0A Commutating Choke, 450A, 690V, 3-Ph

MPN4EU3921-6AA00-0A

Siemens 4EU3921-6AA00-0A commutating choke for converters, 3-phase, 690V AC, 450A rated current, 500A max, IP00, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3921-6AA00-0A — Inductance & Impedance
ParameterValue
Rated inductance0.000094H
Relative inductive voltage drop4%
4EU3921-6AA00-0A — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU3921-6AA00-0A — Electrical
ParameterValue
Rated operating voltage690V
Number of phases3
Rated current (DC)612.7A
Voltage typeAC
Rated operating frequency50Hz
4EU3921-6AA00-0A — Losses & Thermal
ParameterValue
Power loss, coil (W)378W
Power loss, iron core (W)223W
Rated ambient temperature40°C
4EU3921-6AA00-0A — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3921-6AA00-0A — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.385m
Width0.41m
Depth0.229m

Product details

The Siemens 4EU3921-6AA00-0A is a 3-phase commutating choke for converter applications, rated 450 A continuous with a maximum of 500 A at 690 V AC, 50 Hz. The 0.000094 H inductance limits the rate of current rise during thyristor commutation, which reduces di/dt stress on the converter's semiconductors and suppresses line notching.

The 450 A rated current and 690 V AC operating voltage define the continuous thermal load. That heat must be removed from the enclosure; IP00 means no ingress protection, so the choke is intended for mounting inside a clean, ventilated cabinet where convection or forced air handles the thermal budget. The DC rated current of 612.7 A is higher than the AC rating because the RMS current in a DC link is lower for the same copper loss — a detail that matters when the choke is used on the DC side of a 6-pulse or 12-pulse rectifier.

Deployment context

This choke mounts inside a converter cabinet via its flat-type terminals — no DIN rail, no snap-on. Thermal class H insulation (180 °C hot-spot) per IEC 60085 gives headroom for overload cycles common in drive and rectifier applications.

Frequently asked questions

Where can I buy 4EU3921-6AA00-0A and get a price?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What are the key electrical ratings of 4EU3921-6AA00-0A?

450 A rated current, 500 A maximum, 690 V AC, 3-phase, 50 Hz, 0.000094 H inductance, 4% relative inductive voltage drop.

What is the physical size of this choke?

0.385 m height, 0.41 m width, 0.229 m depth.

MPN
4EU3921-6AA00-0A