The 100 kvar reactive power rating and 134 Hz resonant frequency indicate a filter tuned for harmonic mitigation. The IP00 enclosure means it's an open-frame component — no drip shield, no finger guard. It mounts inside a cabinet, not on the wall in a wet area.
Thermal class H per IEC 60085 means the winding insulation can sustain 180 °C hot-spot temperature continuously. That's a full grade above the more common class F (155 °C). For a reactor dissipating 450 W of heat into the enclosure, class H gives you a wider safety margin if the panel runs warm or the duty cycle is heavy — you won't cook the winding as fast. Factor it into the thermal budget. The 40 °C ambient temperature rating is the standard IEC derating baseline. Derate current above that.
The reactor measures 0.229 m deep, 0.41 m wide, and 0.385 m tall. It bolts to a mounting plate.