Skip to main content
Siemens 4EU3951-0AS00-0A — Line/Load Reactors

Siemens SIDAC 4EU3951-0AS00-0A Output Reactor, 200A, 0.2 mH

MPN4EU3951-0AS00-0A

Siemens SIDAC output reactor, 3-phase, 200 A max, 0.2 mH, IP00, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3951-0AS00-0A — Inductance & Impedance
ParameterValue
Rated inductance0.0002H
4EU3951-0AS00-0A — Identification
ParameterValue
Product designationoutput reactor
4EU3951-0AS00-0A — Electrical
ParameterValue
Number of phases3
Voltage typeAC
4EU3951-0AS00-0A — Losses & Thermal
ParameterValue
Rated ambient temperature40°C
4EU3951-0AS00-0A — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3951-0AS00-0A — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.38m
Width0.41m
Depth0.22m
4EU3951-0AS00-0A — Other specifications
ParameterValue
Rated value3 200Hz

Product details

The Siemens SIDAC 4EU3951-0AS00-0A is a 3-phase output reactor rated for 200 A maximum continuous current with 0.2 mH inductance per phase, designed to sit between a variable-frequency drive and the motor cable. The 0.2 mH inductance limits the rate of current rise from the drive's PWM output, reducing voltage spikes that stress motor winding insulation — especially on long cable runs or with older motors. Rated switching frequency of 3.2 kHz matches the typical carrier frequency of many general-purpose drives.

Open-frame IP00 construction — no enclosure, so it mounts inside a cabinet on a backplate or mounting rail. Dimensions are 0.41 m wide by 0.38 m tall by 0.22 m deep, which is a substantial footprint; plan for adequate clearance around the flat-type terminals (0.2–2.5 mm² stranded or solid) for wrench access. Class H insulation (180 °C) means the reactor can run hot without degrading the winding varnish, which is typical for reactors in continuous-duty VFD applications. Ambient temperature rated at 40 °C; derate current if cabinet ambient exceeds that.

Frequently asked questions

What is the 4EU3951-0AS00-0A used for?

It's a 3-phase output reactor (choke) placed between a variable-frequency drive and the motor to smooth the PWM waveform, reduce dv/dt stress on motor windings, and limit capacitive coupling currents in long cable runs.

Where can I buy the 4EU3951-0AS00-0A?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

What are the key electrical ratings of 4EU3951-0AS00-0A?

200 A maximum continuous current, 0.2 mH inductance, 3.2 kHz switching frequency, 420 V rated voltage, 3-phase AC.

MPN
4EU3951-0AS00-0A