Skip to main content
Siemens 4EU3951-3UB00-0A

Siemens 4EU3951-3UB00-0A Mains Choke, 560A, 500V AC, 50Hz

MPN 4EU3951-3UB00-0A

Siemens SENTRON 4EU3951-3UB00-0A mains choke for frequency converters, 3-phase, 500V AC, 50Hz, 560A max / 504A rated, 65µH, 4% voltage drop, IP00, flat-type terminals, Class H insulation.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

4EU3951-3UB00-0A specifications
ParameterValue
IP ratingIP00
Depth0.229 m
Width0.41 m
Height0.385 m

Product details

The Siemens 4EU3951-3UB00-0A is a three-phase mains choke (Netzdrossel f. FU) designed for the input side of a frequency converter. It smooths line current, reduces harmonic distortion, and limits inrush current peaks that would otherwise stress the drive's DC bus capacitors. Rated for 504 A continuous with a 560 A maximum, it handles the full-load current of a large drive without saturating. The 500 V AC operating voltage and 50 Hz line frequency match standard European industrial mains. The 65 µH inductance and 4 % relative inductive voltage drop are the key sizing parameters — they determine how much line impedance the choke adds, which governs the harmonic attenuation and the voltage sag the drive sees under load.

Thermal and construction details

Total power loss is 730 W — 540 W in the coil and 190 W in the iron core — all dissipated as heat. Class H insulation (180 °C thermal class per IEC 60085) means the winding can run hot without degrading; still, the panel builder needs to account for that heat load in the enclosure ventilation. IP00 protection class means it is an open-frame component — no housing, no splash protection. Main circuit connections are flat-type terminals (bus-bar style), not screw clamps. That means the installer needs a bus-bar or a flat-cable lug kit — standard ring terminals won't fit.

Because it is a mature, high-current line reactor with UL/CSA recognition per EN 61558-2-20, it is still widely specified for drive panels that need a listed input choke.

Physical footprint

Dimensions are 0.229 m deep, 0.41 m wide, and 0.385 m tall — roughly 9 by 16 by 15 inches. That is a substantial block; verify the cabinet depth and backplate space before committing the panel layout.

MPN
4EU3951-3UB00-0A