Skip to main content
Siemens 4EU3951-4UA00-0A — Line/Load Reactors

Siemens 4EU3951-4UA00-0A Mains Choke, 900A Rated, 690V, IP00

MPN4EU3951-4UA00-0A

Siemens SENTRON 4EU3951-4UA00-0A mains choke for frequency converters, 3-phase, 690V AC, 900A rated current, 0.025 mH, IP00, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3951-4UA00-0A — Inductance & Impedance
ParameterValue
Rated inductance0.000025H
Relative inductive voltage drop2%
4EU3951-4UA00-0A — Identification
ParameterValue
Product designationNetzdrossel f. FU
4EU3951-4UA00-0A — Electrical
ParameterValue
Rated operating voltage690, 690V
Number of phases3
Voltage typeAC
Rated operating frequency60 ... 50Hz
4EU3951-4UA00-0A — Losses & Thermal
ParameterValue
Power loss, coil (W)380W
Power loss, iron core (W)190W
Rated ambient temperature40°C
4EU3951-4UA00-0A — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3951-4UA00-0A — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.385m
Width0.41m
Depth0.229m

Product details

What this mains choke delivers on a drive line

The Siemens 4EU3951-4UA00-0A is a 3-phase mains choke (Netzdrossel f. FU) rated for 900 A continuous with a maximum of 1 000 A, built to sit between the supply and a frequency converter's input. At 690 V AC and 50/60 Hz it's sized for heavy industrial drives, not small VFD cabinets. Rated current is 900 A; maximum is 1 000 A. Coil loss is 380 W, iron-core loss is 190 W at 40 °C ambient.

IP00 means no enclosure — this is a panel-mount component that needs a cabinet for protection. Dimensions are 0.41 m wide, 0.385 m tall, 0.229 m deep — plan the mounting footprint and busbar clearance accordingly. Thermal class H per IEC 60085 means the insulation system withstands 180 °C hot-spot temperature. That's standard for line reactors in high-ambient drive panels, but confirm the enclosure ventilation moves enough air to keep the 570 W heat rise within the panel's rating.

The part carries EN 61558-2-20 as the choke standard. No UL listing is stated in the evidence.

Frequently asked questions

What is the physical size of the 4EU3951-4UA00-0A?

The choke measures 0.41 m wide, 0.385 m tall, and 0.229 m deep. It is IP00-rated with flat-type terminals, so it requires an enclosure and busbar connections.

MPN