It handles a maximum AC current of 1,310 A and carries a rated inductance of 18 µH. Total power loss breaks down to 680 W in the coil and 325 W in the iron core, so plan for about 1 kW of heat rejection in the enclosure. The Class H insulation (180°C thermal class per IEC 60085) gives headroom for high-ambient or overload conditions, but the IP00 rating means this is an open-frame component — it needs a cabinet or panel for protection against dust and contact.
Sizing and integration
Footprint is 0.46 m wide by 0.435 m tall by 0.265 m deep. Flat-type terminals expect busbar or cable lugs. The DC rated current of 1,605.3 A is higher than the AC maximum, which is typical for a commutating choke — the DC link sees continuous current while the AC side sees the RMS of a pulsed waveform. If your converter's DC bus current exceeds 1,605 A, this choke saturates; size up.