Skip to main content
Siemens 4EU4321-2BA00-0A — Line/Load Reactors

4EU4321-2BA00-0A Commutating Choke, 504A, 750V AC, 98µH

MPN4EU4321-2BA00-0A

Siemens 4EU4321-2BA00-0A commutating choke for converters, 3-phase, 504 A rated current, 750 V AC, 98 µH, IP00 open-frame.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU4321-2BA00-0A — Inductance & Impedance
ParameterValue
Rated inductance0.000098H
Relative inductive voltage drop4%
4EU4321-2BA00-0A — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU4321-2BA00-0A — Electrical
ParameterValue
Rated operating voltage750V
Number of phases3
Rated current (DC)686.2A
Voltage typeAC
Rated operating frequency50Hz
4EU4321-2BA00-0A — Losses & Thermal
ParameterValue
Power loss, coil (W)474W
Power loss, iron core (W)313W
Rated ambient temperature40°C
4EU4321-2BA00-0A — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU4321-2BA00-0A — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.435m
Width0.46m
Depth0.265m

Product details

Line-side filtering for converter harmonics

The Siemens 4EU4321-2BA00-0A is a 3-phase commutating choke (line reactor) sized for converter input circuits — it sits between the supply and the drive rectifier to limit current rise rates and reduce harmonic distortion. Rated at 504 A continuous with a maximum of 560 A, and wound for 750 V AC at 50 Hz, it delivers 98 µH inductance with a 4 % relative inductive voltage drop at rated conditions. Open-frame (IP00) construction means this choke is intended for enclosure mounting where the panel provides the environmental seal — not for standalone outdoor or washdown duty. Thermal class H insulation (180 °C rated) keeps the winding safe under full load, with a combined copper and iron loss of 787 W (474 W coil + 313 W core) that must be ventilated out of the cabinet.

The 504 A rated current (at 40 °C ambient) defines the continuous load capacity — match this to the drive's input current, not the motor FLA. The 560 A maximum is the thermal overload ceiling; sustained operation above 504 A requires derating or forced cooling. At 750 V AC line-to-line, the choke handles standard 400 V and 690 V drives with headroom. The 98 µH inductance and 4 % voltage drop are tuned for typical 6-pulse rectifier commutation — lower inductance would increase harmonic content, higher would drop more voltage across the choke under load. Power dissipation of 787 W means this is not a small component to ignore in thermal design — the panel must move that heat out.

Frequently asked questions

Where can I buy 4EU4321-2BA00-0A and get a price?

This part is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

What are the key electrical ratings for this choke?

Rated current 504 A, maximum current 560 A, rated voltage 750 V AC, inductance 98 µH, relative inductive voltage drop 4 %, power dissipation 787 W total.

MPN
4EU4321-2BA00-0A