Skip to main content
Siemens 4EU4321-5CA00-0A — Line/Load Reactors

Siemens 4EU4321-5CA00-0A Commutating Choke, 900 A, 500 V AC

MPN4EU4321-5CA00-0A

Siemens 4EU4321-5CA00-0A commutating choke for converter, 3-phase, 500 V AC, 900 A rated current, 29 µH, IP00, flat-type terminals, UL/CSA recognized.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EU4321-5CA00-0A — Inductance & Impedance
ParameterValue
Rated inductance0.000029H
Relative inductive voltage drop4%

Identification

4EU4321-5CA00-0A — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter

Electrical

4EU4321-5CA00-0A — Electrical
ParameterValue
Rated operating voltage500V
Number of phases3
Rated current (DC)1 225.4A
Voltage typeAC
Rated operating frequency50Hz
Peak current1 250A

Losses & Thermal

4EU4321-5CA00-0A — Losses & Thermal
ParameterValue
Power loss, coil (W)480W
Power loss, iron core (W)274W
Rated ambient temperature40°C

Approvals

4EU4321-5CA00-0A — Approvals
ParameterValue
Thermal class (IEC 60085)H

Mechanical

4EU4321-5CA00-0A — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.435m
Width0.46m
Depth0.265m

Product details

The Siemens 4EU4321-5CA00-0A is a 3-phase commutating choke for converter applications, rated 900 A continuous with a peak current capability of 1 250 A. It operates at 500 V AC, 50 Hz, and provides 29 µH inductance with a 4% relative inductive voltage drop at rated current. The choke is designed for use in power conversion circuits where it limits di/dt and reduces harmonic stress on semiconductors.

Key Ratings and What They Mean

The 900 A rated current is the continuous thermal current at 40 °C ambient — this is the line current the choke can carry without exceeding its thermal class H insulation. The 1 250 A peak rating covers transient overloads typical during converter startup or fault clearing. Inductance of 29 µH with a 4% voltage drop at rated current means the choke introduces a predictable impedance into the converter commutation path, limiting current rise rates and protecting the switching devices. The 480 W coil loss plus 274 W iron core loss total 754 W — factor this heat into your enclosure ventilation. IP00 protection class means the choke is open-frame — no ingress protection. It must be mounted inside a cabinet with adequate clearance and cooling. Flat-type terminals accept busbar or cable lugs; plan for bolted connections, not spring clamps.

Where It Is Used

This choke sits between the converter (VFD or DC drive) and the supply line, or in the DC link, to suppress commutation notches and limit fault current. Common in industrial drive systems for pumps, conveyors, and compressors where a 3-phase 500 V AC supply feeds a converter rated near 900 A.

Frequently asked questions

Where can I buy 4EU4321-5CA00-0A and get a price?

We source this part to order against an RFQ. Submit a request and we will confirm availability and current pricing — no stock or price figures are published here.

What are the key specifications of 4EU4321-5CA00-0A?

Rated current 900 A, peak current 1 250 A, inductance 29 µH, rated voltage 500 V AC, 3-phase, 50 Hz, IP00, thermal class H, flat-type terminals, UL/CSA recognized.

MPN