Skip to main content
Siemens 4EU4321-6DA00-0A — Line/Load Reactors

Siemens 4EU4321-6DA00-0A Commutating Choke, 720A, 750V

MPN4EU4321-6DA00-0A

Siemens 4EU4321-6DA00-0A commutating choke for converter, 3-phase, 720A rated current, 750V AC, 50Hz, IP00, flat-type terminals.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Inductance & Impedance

4EU4321-6DA00-0A — Inductance & Impedance
ParameterValue
Rated inductance0.000055H
Relative inductive voltage drop4%

Identification

4EU4321-6DA00-0A — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter

Electrical

4EU4321-6DA00-0A — Electrical
ParameterValue
Rated operating voltage750V
Number of phases3
Rated current (DC)980.3A
Voltage typeAC
Rated operating frequency50Hz
Peak current1 000A

Losses & Thermal

4EU4321-6DA00-0A — Losses & Thermal
ParameterValue
Power loss, coil (W)480W
Power loss, iron core (W)285W
Rated ambient temperature40°C

Approvals

4EU4321-6DA00-0A — Approvals
ParameterValue
Thermal class (IEC 60085)H

Mechanical

4EU4321-6DA00-0A — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.435m
Width0.46m
Depth0.265m

Product details

The Siemens 4EU4321-6DA00-0A is a 3-phase commutating choke for converter applications, rated for 720 A continuous with a maximum of 800 A and a peak current capability of 1 000 A. It operates at 750 V AC, 50 Hz, and carries an inductance of 0.000055 H. The 4% relative inductive voltage drop at rated current is the key parameter for sizing the DC-link — it determines how much voltage headroom the drive loses across the choke under load.

Sizing and thermal reality

Total power loss at rated load is 480 W coil plus 285 W iron core. At IP00, heat dissipates into cabinet air — plan forced ventilation if ambient exceeds 40 °C.

Lifecycle and sourcing posture

This part carries a mature lifecycle status. It is sourced and quoted to order against an RFQ through independent distribution.

Physical fit and connections

Dimensions: 0.46 m wide × 0.435 m high × 0.265 m deep. Main circuit connections are flat-type terminals. IP00 rating means no integral enclosure.

Frequently asked questions

What approvals does 4EU4321-6DA00-0A carry?

The listing notes UL/CSA recognition per EN 61558-2-20. That covers the safety standard for chokes and transformers in North American and European installations.

MPN
4EU4321-6DA00-0A