Siemens 4EU4351-0UC00-0A — Line/Load Reactors

Siemens 4EU4351-0UC00-0A Mains Choke, 1120 A, 460 V, 60 Hz

MPN4EU4351-0UC00-0A

Siemens 4EU4351-0UC00-0A mains choke for frequency converters, 3-phase, 460 V AC, 60 Hz, 1008 A rated / 1120 A max, 25 µH, IP00, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU4351-0UC00-0A — Inductance & Impedance
ParameterValue
Rated inductance0.000025H
Relative inductive voltage drop4%
4EU4351-0UC00-0A — Identification
ParameterValue
Product designationNetzdrossel f. FU
4EU4351-0UC00-0A — Electrical
ParameterValue
Rated operating voltage460V
Number of phases3
Voltage typeAC
Rated operating frequency60Hz
4EU4351-0UC00-0A — Losses & Thermal
ParameterValue
Power loss, coil (W)459W
Power loss, iron core (W)364W
Rated ambient temperature40°C
4EU4351-0UC00-0A — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU4351-0UC00-0A — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.435m
Width0.46m
Depth0.265m

Product details

Line reactor for 460 V drive systems

The Siemens 4EU4351-0UC00-0A is a three-phase mains choke (line reactor) designed for the input side of frequency converters operating at 460 V AC, 60 Hz. It carries a rated continuous current of 1008 A and a maximum current of 1120 A at 60 Hz, with a rated inductance of 25 µH and a relative inductive voltage drop of 4% at rated conditions. The 4% impedance is a typical value for drive input chokes, providing enough harmonic attenuation to protect the converter DC bus without excessive voltage drop under load. Rated for a 40 °C ambient with Class H insulation (180 °C thermal class per IEC 60085), this choke dissipates 459 W in the coil and 364 W in the iron core at full load — total 823 W of heat that must be removed from the enclosure.

Integration into a drive line-up

The choke measures 0.46 m wide × 0.435 m high × 0.265 m deep — a substantial footprint that requires floor-mounting or a heavy-duty shelf inside the cabinet. Main circuit connections are via flat-type terminals, which typically accept busbar or large cable lugs. The 1120 A maximum rating means this choke pairs with drives in the 500–600 hp range at 460 V; verify that the drive manufacturer's recommended line reactor impedance matches the 4% value.

Frequently asked questions

What are the key electrical ratings of 4EU4351-0UC00-0A?

Rated voltage 460 V AC, 60 Hz, three-phase. Rated continuous current 1008 A, maximum current 1120 A. Inductance 25 µH, relative voltage drop 4%. Total power loss 823 W at full load.

What compliance standards does this choke meet?

Designed to EN 61558-2-20 for chokes. Insulation class H per IEC 60085. Protection class IP00.

Where can I buy 4EU4351-0UC00-0A?

This part is sourced and quoted to order against an RFQ through independent industrial automation distribution. Availability and current pricing are confirmed at quote time.

MPN