Skip to main content
Siemens 4EU4351-5UA00-0A — Line/Load Reactors

Siemens 4EU4351-5UA00-0A Mains Choke, 910A, 3-Phase, IP00

MPN4EU4351-5UA00-0A

Siemens 4EU4351-5UA00-0A mains choke for frequency converters, 3-phase, 500V AC, 910A max / 819A rated, 0.04 mH, 4% voltage drop, IP00, flat-type terminals, UL/CSA recognized.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU4351-5UA00-0A — Inductance & Impedance
ParameterValue
Rated inductance0.00004H
Relative inductive voltage drop4%
4EU4351-5UA00-0A — Identification
ParameterValue
Product designationNetzdrossel f. FU
4EU4351-5UA00-0A — Electrical
ParameterValue
Rated operating voltage500V
Number of phases3
Voltage typeAC
Rated operating frequency50Hz
4EU4351-5UA00-0A — Losses & Thermal
ParameterValue
Power loss, coil (W)670W
Power loss, iron core (W)260W
Rated ambient temperature40°C
4EU4351-5UA00-0A — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU4351-5UA00-0A — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.435m
Width0.46m
Depth0.265m

Product details

Its job is to smooth the current drawn from the supply, limit harmonic distortion, and reduce the peak inrush current that can trip upstream breakers or stress the DC bus capacitors. At 910 A maximum and 819 A rated current on a 500 V AC, 50 Hz line, this is a heavy industrial choke sized for a large drive — think multi-megawatt pumps, conveyors, or compressor trains.

The 0.04 mH inductance and 4 % relative inductive voltage drop tell you the impedance this choke presents at 50 Hz. That 4 % drop is the sweet spot for most drive applications — enough to smooth the line current and limit harmonics without dragging the DC bus voltage down so far the drive trips on undervoltage under load. Either way, the choke needs forced air or generous free air around it — IP00 means no enclosure, so it's an open-frame component meant for a ventilated cabinet.

Thermal and connection details

That's a lot of heat to manage; the panel builder needs to account for this in the cabinet thermal budget. Insulation is Class H per IEC 60085, meaning the winding can handle a 180 °C hot-spot temperature, which is standard for high-current chokes that run warm. Connections are flat-type terminals (bus-bar style), not screw clamps — expect to bolt copper bars or lugs directly to the choke.

MPN