Skip to main content
Siemens 4EU4521-0AK00 — Line/Load Reactors

Siemens 4EU4521-0AK00 Commutating Choke, 1310A AC, 575V, 3-P

MPN4EU4521-0AK00

Siemens 4EU4521-0AK00 commutating choke for converter, 3-phase, 575V AC, 1310A AC rated current, 24µH, IP00, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

4EU4521-0AK00 — Inductance & Impedance
ParameterValue
Rated inductance2.4E-5H
Relative inductive voltage drop4%
4EU4521-0AK00 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU4521-0AK00 — Electrical
ParameterValue
Rated operating voltage575, 575V
Rated current (AC)1 310A
Number of phases3
Current (AC), max.1 310A
Rated current (DC)1 605.3A
Voltage typeAC
Rated operating frequency60 ... 50Hz
Peak current1 638A
4EU4521-0AK00 — Losses & Thermal
ParameterValue
Power loss, coil (W)700W
Power loss, iron core (W)404W
Rated ambient temperature40°C
4EU4521-0AK00 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU4521-0AK00 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.435m
Width0.46m
Depth0.293m

Product details

The Siemens 4EU4521-0AK00 is a 3-phase commutating choke for converter applications, rated for 1310 A AC at 575 V with an inductance of 24 µH. This is the line reactor that sits between the drive and the motor or between the supply and the drive — it limits current rise during commutation, reduces harmonic distortion, and protects the converter's semiconductors from di/dt stress.

The peak current rating of 1638 A gives you the short-term overload capability; a drive drawing 1310 A RMS will see peak currents approaching that during regenerative braking or fault clearing. The DC rated current of 1605.3 A applies when the choke is used on the DC link side of a converter, which is less common but supported. IP00 means no enclosure — this is a panel-mount component that needs to be inside a cabinet with its own IP rating. The flat-type terminals accept busbar or cable lugs; plan for 0.46 m width and 0.435 m height on the mounting surface, with 0.293 m depth projecting into the cabinet. The 700 W coil loss plus 404 W iron core loss means roughly 1.1 kW of heat to vent — factor that into your cabinet cooling calculation.

Deployment context

This choke is sized for large 3-phase converter systems — think 500–800 kW drives feeding pumps, conveyors, or compressors in industrial plants. The 575 V rating matches North American 600 V class systems (575 V is the standard nominal voltage for Canadian and some US industrial grids). The 50/60 Hz frequency rating means it works on either supply; the inductance value is the same at both frequencies, but the 4% voltage drop is measured at the rated frequency.

Frequently asked questions

How do I get pricing and availability for 4EU4521-0AK00?

Submit an RFQ through this listing. We source this part through independent distribution and confirm current pricing and lead time at quote time — no automated stock figures here.

What are the key specifications of 4EU4521-0AK00?

It is a 3-phase commutating choke rated 1310 A AC at 575 V, 24 µH inductance, 4% inductive voltage drop, IP00, with flat-type terminals. Thermal class H insulation, 40 °C ambient rating.

What compliance documentation is available for 4EU4521-0AK00?

The part is VDE 0532 certified and UL/CSA-recognized per the manufacturer description. RoHS and REACH compliance documentation should be available from Siemens upon request.

MPN
4EU4521-0AK00