Siemens 4EU4521-0BH10 — Line/Load Reactors

Siemens 4EU4521-0BH10 Commutating Choke, 1800 A, 3-Phase, 50

MPN4EU4521-0BH10

Siemens 4EU4521-0BH10 commutating choke for converter, 3-phase, 500 V AC, 1800 A rated, 50 Hz, IP00, flat-type terminals, class H insulation.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU4521-0BH10 — Inductance & Impedance
ParameterValue
Rated inductance0.000016H
Relative inductive voltage drop4%
4EU4521-0BH10 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU4521-0BH10 — Electrical
ParameterValue
Rated operating voltage500V
Number of phases3
Rated current (DC)2 205.8A
Voltage typeAC
Rated operating frequency50Hz
4EU4521-0BH10 — Losses & Thermal
ParameterValue
Power loss, coil (W)700W
Power loss, iron core (W)400W
Rated ambient temperature40°C
4EU4521-0BH10 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU4521-0BH10 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.435m
Width0.46m
Depth0.293m

Product details

The Siemens 4EU4521-0BH10 is a 3-phase commutating choke (line reactor) for converter drives, rated for 1800 A continuous at 500 V AC, 50 Hz. It limits current rise and harmonics on the line side of a thyristor or IGBT converter, protecting both the drive and the upstream transformer.

The DC rating of 2205.8 A tells you the choke can handle higher current under DC-link ripple conditions, but the AC-3 motor-duty current governs the real-world sizing for a 3-phase converter output. Total power loss sums to 1100 W (700 W coil + 400 W iron core), which must be dissipated into the enclosure air; this is not a sealed-panel part.

IP00 open-frame construction means the choke has no enclosure — it mounts inside a cabinet or converter cubicle, with live busbars and terminals exposed. The flat-type main-circuit connectors accept busbar or cable lugs; plan for a dedicated mounting plate or chassis rail. Dimensions are 0.46 m wide by 0.435 m tall by 0.293 m deep — verify the cabinet depth and clearance for the 1100 W heat dissipation before committing the panel layout.

Frequently asked questions

What are the key specifications of 4EU4521-0BH10?

It is a 3-phase commutating choke rated 1800 A continuous at 500 V AC, 50 Hz, with 0.000016 H inductance and 4% inductive voltage drop. DC rating is 2205.8 A. Total power loss is 1100 W. Insulation class H (180 °C). IP00 open-frame. Dimensions: 0.46 m wide × 0.435 m tall × 0.293 m deep.

Where can I buy 4EU4521-0BH10 and how is it quoted?

This part is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — it is not a standard stock item and is quoted per request.

What compliance documentation is available for 4EU4521-0BH10?

The evidence does not list specific compliance certifications (RoHS, REACH, UL, IEC). The part is designed per VDE 0532 (transformer/reactor standard). For project documentation, request the manufacturer's declaration at quote time.

MPN
4EU4521-0BH10