Skip to main content
Siemens 4EU4521-0BM10 — Line/Load Reactors

Siemens 4EU4521-0BM10 Commutating Choke, 804 A / 830 V, 50 H

MPN4EU4521-0BM10

Siemens SENTRON 4EU4521-0BM10 commutating choke for converter, 3-phase, 804 A rated current, 830 V AC, 50 Hz, IP00, Class H insulation, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU4521-0BM10 — Inductance & Impedance
ParameterValue
Rated inductance0.000061H
Relative inductive voltage drop4%
4EU4521-0BM10 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU4521-0BM10 — Electrical
ParameterValue
Rated operating voltage830V
Number of phases3
Rated current (DC)985.2A
Voltage typeAC
Rated operating frequency50Hz
4EU4521-0BM10 — Losses & Thermal
ParameterValue
Rated ambient temperature40°C
4EU4521-0BM10 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU4521-0BM10 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.435m
Width0.46m
Depth0.293m

Product details

The Siemens 4EU4521-0BM10 is a commutating choke (line reactor) designed for the DC link or AC input of a three-phase converter drive. It smooths current ripple and limits di/dt during commutation, protecting the converter's semiconductor switches. Rated 804 A continuous at 830 V AC, 50 Hz, with an inductance of 0.061 mH and a relative inductive voltage drop of 4 % at rated current — sized for a heavy-duty drive line. The 804 A rating is the continuous thermal current (Ith) at 40 °C ambient; derate for higher ambient or non-sinusoidal waveforms. The 4 % voltage drop means the choke is a standard impedance match for most 400–690 V class drives — it won't starve the DC bus of voltage under load.

IP00 open-frame construction — no enclosure, no touch protection. Must be mounted inside a cabinet with appropriate clearance to grounded metal and live parts. Footprint 0.46 m wide × 0.435 m tall × 0.293 m deep; flat-type terminals for the main circuit accept busbar or large cable lugs. Plan for bottom-entry cabling or busbar drop from the converter output. Class H insulation (180 °C thermal class per IEC 60085) means the choke can run hot without degrading the winding — typical for high-current line reactors in continuous-duty drives. Still, keep the ambient below 40 °C for full 804 A rating.

Frequently asked questions

How do I get current pricing and availability for 4EU4521-0BM10?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time; the part is sourced to order through independent distribution channels.

What is the footprint of 4EU4521-0BM10?

The choke measures 0.46 m wide × 0.435 m tall × 0.293 m deep, with flat-type terminals for the main circuit.

What is the 804 A rating based on?

The 804 A is the continuous thermal current (Ith) at 40 °C ambient, 50 Hz, with a 4 % inductive voltage drop. It is also the rated current for the DC link application.

MPN
4EU4521-0BM10