Skip to main content
Siemens 4EU4521-0UB10-0B — Line/Load Reactors

Siemens 4EU4521-0UB10-0B Mains Choke, 2000 A, 690 V, 3-Phase

MPN4EU4521-0UB10-0B

Siemens 4EU4521-0UB10-0B Netzdrossel f. FU, 3-phase, 690 V AC, 2000 A, 50 Hz, 2% voltage drop, IP00, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU4521-0UB10-0B — Inductance & Impedance
ParameterValue
Rated inductance0.000013H
Relative inductive voltage drop2%
4EU4521-0UB10-0B — Identification
ParameterValue
Product designationNetzdrossel f. FU
4EU4521-0UB10-0B — Electrical
ParameterValue
Rated operating voltage690V
Number of phases3
Voltage typeAC
Rated operating frequency50Hz
4EU4521-0UB10-0B — Losses & Thermal
ParameterValue
Power loss, coil (W)680W
Power loss, iron core (W)300W
Rated ambient temperature40°C
4EU4521-0UB10-0B — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU4521-0UB10-0B — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.435m
Width0.46m
Depth0.293m

Product details

Mains choke for 2000 A frequency converter lines

The Siemens 4EU4521-0UB10-0B is a three-phase mains choke (Netzdrossel f. FU) rated for 2000 A continuous at 690 V AC, 50 Hz. It is designed to sit between the supply and a frequency converter drive, limiting harmonic distortion and reducing voltage notching on the line side.

The 2000 A rating (both maximum and rated value) sets the continuous current capacity — this choke is sized for large drives, typically 800 kW to 1 MW class on 690 V systems. The 690 V operating voltage covers 400 V and 690 V line supplies common in European industrial networks. Inductance is 13 µH (0.000013 H), which combined with the 2 % voltage drop gives the impedance needed to limit di/dt and reduce harmonic currents from the drive's rectifier stage. Total power loss is 980 W (680 W coil loss + 300 W iron core loss) at 40 °C ambient. This heat must be dissipated — the IP00 open-frame construction means no enclosure; the choke relies on the panel's forced ventilation or natural convection. Class H insulation (180 °C rated) per IEC 60085 gives thermal headroom for overloads and high ambient temperatures inside the cabinet.

Dimensions are 0.460 m wide × 0.435 m high × 0.293 m deep — a substantial footprint requiring a floor-mount or heavy-duty shelf inside the panel. Main circuit connections use flat-type terminals (busbar or large cable lug interface), not spring-cage or screw clamps. The IP00 rating means no ingress protection; install in a clean, dry cabinet with adequate clearance for airflow and arc-flash boundaries.

Frequently asked questions

What are the key ratings of the 4EU4521-0UB10-0B mains choke?

It is a 3-phase choke rated 2000 A at 690 V AC, 50 Hz, with 13 µH inductance and a 2 % voltage drop. Total power loss is 980 W at 40 °C ambient.

Where can I buy the 4EU4521-0UB10-0B and how is it quoted?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote.

What is the physical size of the 4EU4521-0UB10-0B?

The choke measures 0.460 m wide × 0.435 m high × 0.293 m deep.

Will the 4EU4521-0UB10-0B drop into a panel specified around a 5SJ6463-7?

No — the 5SJ6463-7 is a SENTRON miniature circuit breaker (63 A, 4-pole, DIN-rail mount), a completely different class and current rating. The 4EU4521-0UB10-0B is a 2000 A mains choke with flat-type terminals, requiring busbar connections and a floor-mount footprint.

MPN
4EU4521-0UB10-0B