Skip to main content
Siemens 4EU4521-5BA00 — Line/Load Reactors

Siemens 4EU4521-5BA00 Commutating Choke, 1000A 42µH 750V

MPN4EU4521-5BA00

Siemens 4EU4521-5BA00 commutating choke for converter, 3-phase, 1000A rated, 42µH, 750V AC, IP00, 40°C ambient, class H insulation.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU4521-5BA00 — Inductance & Impedance
ParameterValue
Rated inductance0.000042H
Relative inductive voltage drop4%
4EU4521-5BA00 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU4521-5BA00 — Electrical
ParameterValue
Rated operating voltage750, 750V
Number of phases3
Rated current (DC)1 225.4A
Voltage typeAC
Rated operating frequency60 ... 50Hz
Peak current1 250A
4EU4521-5BA00 — Losses & Thermal
ParameterValue
Power loss, coil (W)488W
Power loss, iron core (W)404W
Rated ambient temperature40°C
4EU4521-5BA00 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU4521-5BA00 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.435m
Width0.46m
Depth0.293m

Product details

The Siemens 4EU4521-5BA00 is a 3-phase commutating choke (line reactor) for converter applications, rated 1000 A continuous with a 1250 A peak capability. Open-frame IP00 construction means it mounts inside a cabinet — no washdown or outdoor duty. The 488 W coil loss plus 404 W iron loss at 40 °C ambient need to be ventilated; class H insulation (180 °C) gives thermal headroom if the enclosure runs hot.

Integration notes

Footprint is 0.46 m wide by 0.435 m tall by 0.293 m deep. Flat-type terminals for the main power circuit accept busbar or lug connections — no ring terminals. Mount it on a panel backplate with clearance for airflow around the core; the combined 892 W dissipation (coil + iron) needs forced ventilation in a sealed cabinet. Operating frequency is 50 or 60 Hz; the inductance value is specified at the rated current and frequency, so verify harmonic content if the drive uses a high pulse number.

Frequently asked questions

What are the key ratings for 4EU4521-5BA00?

Rated 1000 A continuous, 1250 A peak, 750 V AC, 42 µH, 4% inductive voltage drop, 40 °C ambient, class H insulation, IP00.

Where can I buy 4EU4521-5BA00 and get current pricing?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What compliance documentation does 4EU4521-5BA00 carry?

The choke is UL and CSA recognized per VDE 0532, and the insulation system complies with IEC 60085 class H.

MPN
4EU4521-5BA00