Skip to main content
Siemens 4EU4551-0AG18-0B — Line/Load Reactors

Siemens SIDAC 4EU4551-0AG18-0B Output Reactor, 745A, 3-Phase

MPN4EU4551-0AG18-0B

Siemens SIDAC output reactor, 3-phase, 745A max, 1250Hz rated, IP23, thermal class H, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU4551-0AG18-0B — Inductance & Impedance
ParameterValue
Rated inductance0.000079H
4EU4551-0AG18-0B — Identification
ParameterValue
Product designationoutput reactor
4EU4551-0AG18-0B — Electrical
ParameterValue
Number of phases3
Voltage typeAC
4EU4551-0AG18-0B — Losses & Thermal
ParameterValue
Power loss, coil (W)671W
Power loss, iron core (W)412W
Rated ambient temperature40°C
4EU4551-0AG18-0B — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU4551-0AG18-0B — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP23
Height0.43m
Width0.46m
Depth0.29m

Product details

Output Reactor for 3-Phase AC Drives

The Siemens SIDAC 4EU4551-0AG18-0B is a 3-phase output reactor rated for 745 A maximum continuous current and a rated frequency of 1250 Hz. It is designed to sit between a variable-frequency drive and the motor, smoothing the PWM waveform and limiting voltage spikes that can degrade motor insulation over time. Inductance of 0.000079 H per phase filters the drive output. Mounting dimensions are 0.46 m wide by 0.43 m tall by 0.29 m deep — verify panel floor space before committing the BOM line.

Thermal and Electrical Ratings

The combined power loss (coil 671 W plus iron core 412 W) totals about 1.08 kW dissipated as heat; factor that into the cabinet ventilation design. The flat-type terminals accept busbar or large cable lugs — no ring-tongue or spring-cage connection. Verify the lug width fits the terminal pad before wiring.

Mature lifecycle status. Sourced to order; availability confirmed at quote time.

Frequently asked questions

What is the 4EU4551-0AG18-0B used for?

It is a 3-phase output reactor (choke) placed between a variable-frequency drive and the motor to filter PWM harmonics, limit voltage spikes, and protect motor insulation on long cable runs.

MPN
4EU4551-0AG18-0B