Skip to main content
Siemens 4EU5021-0AA00 — Line/Load Reactors

Siemens 4EU5021-0AA00 Commutating Choke, 1640 A, 575 V AC

MPN4EU5021-0AA00

Siemens 4EU5021-0AA00 commutating choke for converter, 3-phase, 575 V AC, 1640 A rated, 0.025 mH, IP00, flat-type terminal.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU5021-0AA00 — Inductance & Impedance
ParameterValue
Rated inductance0.000025H
Relative inductive voltage drop4%
4EU5021-0AA00 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU5021-0AA00 — Electrical
ParameterValue
Rated operating voltage575, 575V
Number of phases3
Rated current (DC)2 009.8A
Voltage typeAC
Rated operating frequency60 ... 50Hz
4EU5021-0AA00 — Losses & Thermal
ParameterValue
Power loss, coil (W)1 300W
Power loss, iron core (W)402W
Rated ambient temperature40°C
4EU5021-0AA00 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU5021-0AA00 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.565m
Width0.518m
Depth0.318m

Product details

The Siemens 4EU5021-0AA00 is a commutating choke (also called a line reactor or DC-link choke) designed for converter applications. It handles 1640 A continuous AC current across three phases at 575 V AC, with a DC-rated current of 2009.8 A. The 0.025 mH inductance limits current rise and reduces harmonic distortion on the converter input or output. Rated for 60...50 Hz operation, this choke dissipates 1300 W in the coil and 402 W in the iron core at full load.

This is a panel-mount component with IP00 protection — no enclosure, so it requires a cabinet that keeps dust and moisture off the windings. Dimensions are 0.518 m wide, 0.318 m deep, and 0.565 m high. The flat-type terminals accept busbar or large cable lugs; plan for adequate bending radius and clearance around the connections. Thermal class H (IEC 60085) means the insulation system withstands 180 °C hot-spot temperature — suitable for high-ambient environments up to 40 °C rated ambient. The choke is designed for continuous duty at that rating; forced ventilation in the cabinet is recommended given the 1.7 kW total heat loss.

Frequently asked questions

What is the rated current of 4EU5021-0AA00?

The rated AC current is 1640 A continuous across three phases at 575 V AC; the DC-rated current is 2009.8 A.

Where can I buy 4EU5021-0AA00?

The part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
4EU5021-0AA00