Skip to main content
Siemens 4EU5051-0AA10-0C — Line/Load Reactors

Siemens 4EU5051-0AA10-0C Mains Choke, 680A, 690V, IP00

MPN4EU5051-0AA10-0C

Siemens 4EU5051-0AA10-0C Netzdrossel mains choke, 3-phase, 690 V AC, 680 A, 0.18 mH, IP00, thermal class H.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

4EU5051-0AA10-0C — Inductance & Impedance
ParameterValue
Rated inductance0.00018H
Relative inductive voltage drop11.6%
4EU5051-0AA10-0C — Identification
ParameterValue
Product designationNetzdrossel
4EU5051-0AA10-0C — Electrical
ParameterValue
Rated operating voltage690, 690V
Rated current (AC)680A
Number of phases3
Current (AC), max.680A
Voltage typeAC
Rated operating frequency50 ... 60Hz
4EU5051-0AA10-0C — Losses & Thermal
ParameterValue
Power loss, coil (W)2 440W
Power loss, iron core (W)795W
Rated ambient temperature45°C
4EU5051-0AA10-0C — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU5051-0AA10-0C — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.565m
Width0.518m
Depth0.318m

Product details

The Siemens 4EU5051-0AA10-0C is a mains choke (Netzdrossel) — a three-phase line reactor rated for 690 V AC at 680 A continuous, with an inductance of 0.00018 H and an 11.6% relative inductive voltage drop at rated current and frequency. It operates on 50 to 60 Hz mains, so it covers both standard industrial line frequencies without derating. The 11.6% voltage drop is the key sizing parameter: it defines how much the choke limits inrush current and harmonic distortion on the line side of a drive or converter.

At 0.518 m wide, 0.318 m deep, and 0.565 m tall, this is a large-frame choke — expect dedicated floor-mount or heavy sub-panel space, not a DIN rail clip. IP00 means no enclosure protection: the choke requires installation inside a cabinet that provides the environmental seal. The flat-connector main terminals are sized for bus-bar or large-lug cabling, not spring-cage terminations.

Thermal and lifecycle reality

Rated for 45 °C ambient with thermal class H insulation — the winding can handle a 180 °C hot-spot, which gives headroom in a warm cabinet but still demands the 2440 W coil loss and 795 W iron-core loss be ventilated out.

Sourcing and fit confirmation

The 680 A / 690 V rating pins the choke to large-drive applications. The 0.00018 H inductance and 11.6% voltage drop are the numbers to match against your drive manufacturer's recommended line reactor spec.

Frequently asked questions

What protection class does 4EU5051-0AA10-0C have?

IP00 — it has no built-in ingress protection and must be installed inside a sealed cabinet.

MPN
4EU5051-0AA10-0C