Skip to main content
Siemens 4EU9932-0AM40-0BA0 — Line/Load Reactors

SIDAC 4EU9932-0AM40-0BA0 Filter Reactor, 193A Max, 173A Rate

MPN4EU9932-0AM40-0BA0

SIDAC filter reactor, 3-phase, 400V AC, 50Hz, 193A max / 173A rated, 1.3mH, 5.67% throttling, IP00, screw/flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU9932-0AM40-0BA0 — Inductance & Impedance
ParameterValue
Rated inductance0.0013H
Relative throttling factor5.67%
Filter resonant frequency210Hz
Rated reactive power (filter bank)100 000var
4EU9932-0AM40-0BA0 — Identification
ParameterValue
Product designationfilter reactor
4EU9932-0AM40-0BA0 — Electrical
ParameterValue
Rated operating voltage400V
Number of phases3
Voltage typeAC
Rated operating frequency50Hz
4EU9932-0AM40-0BA0 — Losses & Thermal
ParameterValue
Rated ambient temperature40°C
4EU9932-0AM40-0BA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU9932-0AM40-0BA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector / screw-type terminals
IP protection ratingIP00
4EU9932-0AM40-0BA0 — Other specifications
ParameterValue
Rated value173A

Product details

Line Reactor for 400V AC Drives — 193A Peak, 173A Continuous

The SIDAC 4EU9932-0AM40-0BA0 is a 3-phase filter reactor rated for 400V AC at 50Hz. It carries a maximum current of 193A and a rated continuous current of 173A, with an inductance of 0.0013H and a relative throttling factor of 5.67%.

The 173A rated current is the continuous thermal limit at 40°C ambient — size your drive's input current to stay under this for sustained operation. The 193A maximum is the short-term peak the reactor can handle without saturating; useful for motor starting inrush or momentary overloads. The 5.67% throttling factor (impedance relative to the drive's base load) provides enough line impedance to reduce harmonic distortion and limit di/dt on the drive's input rectifier, but is low enough to avoid excessive voltage drop at full load. The resonant frequency of the filter is 210Hz — well above the 50Hz line fundamental and below typical switching frequencies of 2-16kHz PWM drives, so it won't resonate with the drive's carrier frequency. Thermal class H (180°C) insulation means the reactor can tolerate high internal temperatures without degrading the winding varnish, which matters when it's installed in a warm cabinet near the drive's heat sink.

Panel Integration — Open-Frame Mounting

This is a chassis-mount component — plan for a mounting plate or bracket inside the enclosure. The flat connector style accepts busbar or cable lug connections; torque values per the manufacturer's installation instructions (not listed here, but standard for M8 or M10 hardware on this current class). Allow clearance around the reactor for air circulation — it dissipates heat through natural convection, and thermal class H assumes free airflow.

Frequently asked questions

What is the rated continuous current of 4EU9932-0AM40-0BA0?

The rated continuous current is 173A AC at 40°C ambient. This is the thermal limit for sustained operation.

MPN
4EU9932-0AM40-0BA0