Skip to main content
Siemens 5SJ4106-7HG40 — 1-Pole MCB (DIN Rail)

Siemens 5SJ4106-7HG40 SENTRON MCB, 1P C-Curve 10kA/15kA

MPN5SJ4106-7HG40
Active

Siemens SENTRON 5SJ4 series, 5SJ4106-7HG40, 1-pole miniature circuit breaker, C-curve, 10 kA (EN 60898) / 15 kA (IEC 60947-2), 400 V AC, 60 V DC, 18 mm width.

$27.94 – $79.74Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SJ4106-7HG40 — Identification
ParameterValue
Product designationMiniature circuit breakers
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SJ4106-7HG40 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Overvoltage category3
5SJ4106-7HG40 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodon standard mounting rail
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth70 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SJ4106-7HG40 — Environmental
ParameterValue
IP protection classIP20, with connected conductors, IP 40 in the handle range
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The breaker is rated for 400 V AC and 60 V DC, with a breaking capacity of 10 kA according to EN 60898 and 15 kA according to IEC 60947-2.

Rated insulation voltage (Ui) is 440 V AC, which exceeds the rated operating voltage of 400 V AC. This means the breaker's internal clearances and creepage distances are designed for a 440 V system, providing a safety margin in 400 V networks. The IP20 rating applies with connected conductors; IP40 in the handle range means the toggle area is protected against tools and fingers but the terminals need to be inside an enclosure. The 70 mm depth and 90 mm height are standard for this class — it fits existing SENTRON or third-party distribution boards without clearance issues.

The 18 mm width (1 MW) means it occupies one slot in a distribution board — straightforward to swap in or add to an existing row. The neutral conductor is not switched, so this is a line-only pole; pair it with a separate neutral bar or a 2-pole variant if you need neutral isolation. Vibration resistance is specified at 50 m/s² from 25 to 150 Hz and 60 m/s² at 35 Hz for 4 seconds — adequate for installation on machine-mounted panels or near rotating equipment, but not a heavy-industrial shock spec.

Frequently asked questions

What is the breaking capacity of this MCB?

10 kA per EN 60898 and 15 kA per IEC 60947-2. The higher IEC rating applies in industrial installations where the standard is specified.

What are the physical dimensions of the 5SJ4106-7HG40?

Width 18 mm (1 modular unit), height 90 mm, depth 70 mm. Installation depth is also 70 mm.

Will this breaker fit in a panel designed for the 5SL6006-7?

Both are 1-pole MCBs on a standard DIN rail, same 18 mm width. The 5SJ4106-7HG40 has a higher breaking capacity (15 kA vs the 5SL6006-7's typical 6 kA) and a different tripping curve, so verify the C-curve and SCCR requirements of your panel design before substituting.

MPN
5SJ4106-7HG40