Skip to main content
Siemens 5SJ4111-7HG40 — 1-Pole MCB (DIN Rail)

Siemens 5SJ4111-7HG40 SENTRON MCB, 1P C-curve 10kA

MPN5SJ4111-7HG40
Active

Siemens SENTRON 5SJ4 series miniature circuit breaker, 1-pole, C-curve, 10 kA (EN 60898) / 15 kA (IEC 60947-2), 400 V AC, 60 V DC, 18 mm width, DIN-rail mount.

$77.71Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SJ4111-7HG40 — Identification
ParameterValue
Product designationMiniature circuit breakers
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SJ4111-7HG40 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Overvoltage category3
5SJ4111-7HG40 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodon standard mounting rail
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth70 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SJ4111-7HG40 — Environmental
ParameterValue
IP protection classIP20, with connected conductors, IP 40 in the handle range
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

What this MCB is and what it does

The Siemens 5SJ4111-7HG40 is a 1-pole SENTRON miniature circuit breaker (MCB) with a C-curve tripping characteristic, designed for branch-circuit protection in industrial control panels and distribution boards. It snaps onto a standard 35 mm DIN rail and occupies one modular width (18 mm), so it fits the usual 18 mm-per-pole grid in a panel.

Key ratings and what they mean for fit

Rated at 10 kA breaking capacity per EN 60898 and 15 kA per IEC 60947-2 at 400 V AC. The C-curve (magnetic trip between 5× and 10× In) is the standard choice for moderate inrush loads like small motors, contactor coils, and lighting — it avoids nuisance trips on startup while still clearing a hard fault. The 15 kA rating under IEC 60947-2 is the one that matters for industrial panel SCCR calculations; 10 kA under EN 60898 covers residential and light commercial. Rated insulation voltage (Ui) is 440 V AC, so the breaker is suitable for 400 V line-to-line systems with margin. DC rating is 60 V maximum, which limits its use on DC circuits to single-pole switching at that voltage — fine for control-voltage busses or small DC loads, not for higher-voltage DC strings. Pollution degree 3 and overvoltage category 3 mean it's rated for the industrial environment: conductive pollution can occur, and it handles transient overvoltages typical of fixed-installation distribution.

Mounting and integration

IP20 with connected conductors, IP40 in the handle range — standard for enclosed panel mounting; not rated for washdown or outdoor exposure without an enclosure. Ambient temperature range -40 °C to 75 °C covers most industrial environments, including cold storage and hot machine cabinets. Vibration resistance is specified at 50 m/s² over 25–150 Hz and 60 m/s² at 35 Hz (4 s), which is adequate for general industrial machinery but not for extreme shock loads.

Frequently asked questions

Where can I buy 5SJ4111-7HG40 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) and we will confirm availability and current pricing at quote time.

What is the closest functional second-source to 5SJ4111-7HG40?

The Siemens 5SL6006-7 is a similar 1-pole C-curve MCB in the same SENTRON family, but it has different breaking capacity ratings and a different form factor. The 5SJ4111-7HG40 is the direct 5SJ4 series equivalent. Verify the specific ratings (10 kA EN 60898 / 15 kA IEC 60947-2) against your application before substituting.

What is the depth of 5SJ4111-7HG40?

The installation depth is 70 mm, which is the dimension from the DIN-rail mounting surface to the front of the breaker.

What is the width of 5SJ4111-7HG40?

The width is 18 mm, which is one standard modular unit (1 MW) for DIN-rail components.

Will 5SJ4111-7HG40 drop into a panel specified around 5SL6006-7 without rewiring?

Both are 1-pole C-curve MCBs on a standard 35 mm DIN rail, so the mechanical fit and wiring connections are the same. However, verify the breaking capacity ratings (10 kA EN 60898 / 15 kA IEC 60947-2 for the 5SJ4111-7HG40) match or exceed the original design's SCCR requirements before swapping.

What compliance documentation does Siemens provide for 5SJ4111-7HG40?

As a standard SENTRON MCB, it carries CE marking for the European market and is designed to meet EN 60898 and IEC 60947-2. RoHS and REACH declarations are typically available from Siemens upon request. The part is halogen-free and silicon-free, which supports clean-room and sensitive-environment compliance.

MPN