Skip to main content
Siemens 5SJ4111-7HG41 — 1-Pole MCB (DIN Rail)

Siemens 5SJ4111-7HG41 SENTRON MCB, 1P C-curve, 10 kA

MPN5SJ4111-7HG41
Active

Siemens SENTRON 5SJ4 series, miniature circuit breaker 5SJ4111-7HG41, 1-pole, C-curve, 10 kA (EN 60898) / 15 kA (IEC 60947-2), 400 V AC / 60 V DC, 18 mm width.

$36.83 – $89.59Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SJ4111-7HG41 — Identification
ParameterValue
Product designationMiniature circuit breakers
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SJ4111-7HG41 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Overvoltage category3
5SJ4111-7HG41 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodon standard mounting rail
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height110 mm
Depth70 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SJ4111-7HG41 — Environmental
ParameterValue
IP protection classIP20, with connected conductors, IP 40 in the handle range
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens SENTRON 5SJ4111-7HG41 is a 1-pole miniature circuit breaker with C-curve tripping characteristic, rated 10 kA breaking capacity per EN 60898 and 15 kA per IEC 60947-2 at 400 V AC. The C-curve means it trips between 5 and 10 times rated current — standard for protecting inductive loads like motor starters and contactor coils where inrush is moderate. It is also rated for DC circuits up to 60 V, making it usable in control-voltage distribution.

Compliance and environmental ratings

Rated for overvoltage category III and pollution degree 3, so it is suitable for fixed installations within building distribution or industrial panels where transient overvoltages and conductive dust are expected. The housing is halogen-free and silicon-free, which matters for panels in clean-room or corrosive environments where outgassing must be minimised. IP20 with connected conductors; IP40 in the handle area — standard for panel-mount MCBs, not for wet locations.

Frequently asked questions

What are the key breaking capacity ratings?

10 kA per EN 60898 and 15 kA per IEC 60947-2, both at 400 V AC.

What compliance documentation is available for this MCB?

The part is halogen-free and silicon-free, rated for overvoltage category III and pollution degree 3. It carries the SENTRON brand designation and is designed per EN 60898 and IEC 60947-2. Full declarations of conformity are available from Siemens on request.

MPN
5SJ4111-7HG41