Siemens 5SJ4111-8HG40 — 1-Pole MCB (DIN Rail)

Siemens SENTRON 5SJ4111-8HG40 MCB, 1P, D-curve, 10kA

MPN5SJ4111-8HG40
Active

Siemens SENTRON 5SJ4 series, 5SJ4111-8HG40, 1-pole miniature circuit breaker, D tripping characteristic, 10 kA (EN 60898) / 15 kA (IEC 60947-2), 400 V AC, 60 V DC, DIN-rail mount.

$34.29 – $83.23Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SJ4111-8HG40 — Identification
ParameterValue
Product designationMiniature circuit breakers
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SJ4111-8HG40 — Electrical & Protection
ParameterValue
Tripping characteristic classD
Overvoltage category3
5SJ4111-8HG40 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodon standard mounting rail
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth70 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SJ4111-8HG40 — Environmental
ParameterValue
IP protection classIP20, with connected conductors, IP 40 in the handle range
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

Rated breaking capacity is 10 kA per EN 60898 and 15 kA per IEC 60947-2 at 400 V AC, which covers most industrial distribution boards fed from a 400 V transformer up to that fault level. The DC rating is 60 V, suited for control-circuit protection on 24 V or 48 V DC rails.

Degree of pollution 3 and overvoltage category III — the MCB is rated for the conductive environment inside an industrial enclosure where condensation or light contamination may occur. IP20 with connected conductors, IP40 in the handle range; the handle area is protected against tools, but the terminals need to be inside a closed panel.

Vibration resistance is 50 m/s² at 25–150 Hz and 60 m/s² at 35 Hz, which passes the typical industrial machinery vibration profile.

Frequently asked questions

What is the D tripping characteristic used for?

The D-curve (magnetic trip at 10–20× In) is specified for loads with high inrush current: motor starters, small transformers, solenoid valves, and lighting with electronic ballasts. It avoids nuisance tripping on startup that a B or C curve would see.

What breaking capacity does this MCB have?

Rated breaking capacity is 10 kA per EN 60898 and 15 kA per IEC 60947-2 at 400 V AC. For DC circuits, the rated voltage is 60 V.

Can this MCB be locked out for LOTO?

Yes, the device is sealable, meaning the toggle can be locked in the OFF position with a standard padlock hasp or seal wire for lockout/tagout procedures.

What approvals or compliance documentation does it carry?

The MCB is designed to EN 60898 and IEC 60947-2. It is halogen-free and silicon-free. For specific third-party approvals (UL, CSA, etc.), verify the exact variant against the Siemens certification database, as this listing does not enumerate them.