Skip to main content
Siemens 5SJ4113-7HG42 — 1-Pole MCB (DIN Rail)

Siemens 5SJ4113-7HG42 SENTRON MCB, 1P C-curve, 10kA

MPN5SJ4113-7HG42
Active

Siemens SENTRON 5SJ4 miniature circuit breaker, 1-pole, C-curve, 10 kA (EN 60898), 15 kA (IEC 60947-2), 400 V AC, 18 mm width.

$30.48Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SJ4113-7HG42 — Identification
ParameterValue
Product designationMiniature circuit breakers
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SJ4113-7HG42 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Overvoltage category3
5SJ4113-7HG42 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodon standard mounting rail
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height121 mm
Depth70 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SJ4113-7HG42 — Environmental
ParameterValue
IP protection classIP20, with connected conductors, IP 40 in the handle range
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SJ4113-7HG42 is a SENTRON 5SJ4 miniature circuit breaker — 1-pole, C-curve, rated 10 kA breaking capacity per EN 60898 and 15 kA per IEC 60947-2 at 400 V AC. That 15 kA IEC rating is the one that governs industrial panel coordination: it tells you this MCB can clear a fault up to 15 kA without welding its contacts or venting arc gas into the enclosure, which matters when you're sizing the upstream backup fuse or breaker.

What the ratings mean for fit

C-curve trips between 5× and 10× In — standard for motor-starting and moderate inductive loads where you need inrush headroom without nuisance tripping. At 18 mm width (1 modular unit), it snaps onto standard DIN rail and occupies one slot in any SENTRON distribution board or industrial panel. Pollution degree 3 and overvoltage category 3 mean it's rated for the conductive-dust and transient environment you get in a real factory panel, not just a clean residential loadcenter.

Frequently asked questions

What is the breaking capacity at 400 V AC?

10 kA per EN 60898 and 15 kA per IEC 60947-2. The IEC 60947-2 figure is the one to use for industrial panel coordination as it reflects the higher test duty cycle.

What is the physical size — will it fit a standard DIN-rail panel?

18 mm wide (1 modular unit), 121 mm tall, 70 mm deep. It clips onto standard 35 mm DIN rail and occupies one slot. Depth of 70 mm is the installed depth including terminals, so check your enclosure depth against that figure.

What approvals or compliance documentation does this carry?

The 5SJ4113-7HG42 is rated per EN 60898 and IEC 60947-2. It is halogen-free and silicon-free. The SENTRON series carries CE marking and is UL/CSA recognized through Siemens' global certification. Specific RoHS/REACH declarations are available from Siemens' documentation portal for this order code.

How does the 5SJ4113-7HG42 compare to the 5SL4363-7?

The 5SL4363-7 is a different Siemens MCB series (5SL vs 5SJ4) with different breaking capacity ratings and terminal design. The 5SJ4113-7HG42 uses combined top/bottom terminals and is rated for 15 kA per IEC 60947-2; the 5SL series typically has lower interrupting ratings. They are not direct drop-in replacements — verify the interrupting capacity requirement and terminal type before substituting.

MPN
5SJ4113-7HG42