Skip to main content
Siemens 5SJ4115-8HG40 — 1-Pole MCB (DIN Rail)

Siemens 5SJ4115-8HG40 SENTRON MCB, 1P, D Curve, 1.6 A

MPN5SJ4115-8HG40
Active

Siemens SENTRON 5SJ4 miniature circuit breaker, 1-pole, D characteristic, 1.6 A rated current, 18 mm wide, DIN rail mount, IP20.

$77.30Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SJ4115-8HG40 — Identification
ParameterValue
Product designationMiniature circuit breakers
Brand nameSENTRON
Number of poles1
Application suitabilityMechanical engineering / industry
5SJ4115-8HG40 — Electrical & Protection
ParameterValue
Tripping characteristic classD
Rated value (EN 60898)10 kA
Overvoltage category3
5SJ4115-8HG40 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodon standard mounting rail
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth70 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SJ4115-8HG40 — Environmental
ParameterValue
IP protection classIP20, with connected conductors, IP 40 in the handle range
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SJ4115-8HG40 is a 1-pole miniature circuit breaker from the SENTRON 5SJ4 series, designed for branch-circuit overcurrent protection in industrial control panels and mechanical-engineering equipment. At 40 °C ambient it carries a full 1.6 A continuously; derate to 1.3 A at 60 °C if the panel runs hot.

Snaps onto a standard DIN rail (35 mm) and occupies one modular width (18 mm), so it fits a standard 18 mm slot in a distribution board or enclosure. The combined terminal at top and bottom accepts copper conductors; tighten to 3.5 Nm. Mount in any position — no derating needed for orientation.

IP20 with connected conductors (IP40 in the handle area) means it's protected against solid objects >12 mm but not against water ingress; install inside a sealed enclosure in wet areas. Vibration resistance tested to 50 m/s² over 25–150 Hz, covering typical machine-mounted conditions.

Frequently asked questions

What is the D tripping characteristic on this MCB?

The D curve means the magnetic trip operates at 10 to 20 times the rated current (16 to 32 A for a 1.6 A breaker), designed for loads with high inrush such as small transformers, solenoid banks, and motor starters. The thermal element follows the derating table: 1.6 A up to 40 °C, 1.5 A at 45–50 °C, 1.4 A at 55 °C, 1.3 A at 60 °C.

Where can I buy the 5SJ4115-8HG40?

This part is sourced to order against an RFQ through independent distribution. Submit a request for current pricing and availability — confirmed at quote time.

What compliance documentation is available for this MCB?

The SENTRON 5SJ4 series carries IEC 60898-1 certification for miniature circuit breakers. The housing is halogen-free and silicon-free, meeting typical RoHS/REACH material restrictions. Specific declarations are available on request.

MPN
5SJ4115-8HG40