Siemens 5SJ4116-8HG41 — 1-Pole MCB (DIN Rail)

Siemens SENTRON 5SJ4116-8HG41 MCB, 1-pole D 16 A, 10 kA

MPN5SJ4116-8HG41
Active

Siemens SENTRON 5SJ4 series, miniature circuit breaker, 1-pole, D characteristic, 16 A rated current, 10 kA breaking capacity per EN 60898, 18 mm width, 70 mm depth.

$90.87Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SJ4116-8HG41 — Identification
ParameterValue
Product designationMiniature circuit breakers
Brand nameSENTRON
Number of poles1
Application suitabilityMechanical engineering / industry
5SJ4116-8HG41 — Electrical & Protection
ParameterValue
Tripping characteristic classD
Rated value (EN 60898)10 kA
Overvoltage category3
5SJ4116-8HG41 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodon standard mounting rail
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height110 mm
Depth70 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SJ4116-8HG41 — Environmental
ParameterValue
IP protection classIP20, with connected conductors, IP 40 in the handle range
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

Integrator note

The Siemens SENTRON 5SJ4116-8HG41 is a 1-pole miniature circuit breaker with D tripping characteristic, rated 16 A at 40 °C and 10 kA breaking capacity per EN 60898. Rated for 60 V DC maximum, so it also handles DC control circuits in the same panel. Mounts on standard DIN rail, 18 mm wide (1 modular unit), and accepts supply from either end.

Full 16 A rating holds up to 40 °C ambient. Above that, the continuous current must be reduced: 15.5 A at 45 °C, 15 A at 50 °C, 14.5 A at 55 °C, and 14.1 A at 60 °C. Pollution degree 3 (industrial environment) and overvoltage category III. Vibration tested to 50 m/s² at 25–150 Hz and 60 m/s² at 35 Hz for 4 seconds.

Frequently asked questions

What are the key ratings for this MCB?

1-pole, D characteristic, 16 A rated current (holds to 40 °C), 10 kA breaking capacity per EN 60898 at 400 V AC, and 60 V DC maximum. Width 18 mm, depth 70 mm.

What compliance documentation is available for this part?

The product is designed to EN 60898 (breaking capacity 10 kA) and carries IEC 81346-2 designation F. It is halogen-free and silicon-free. For specific declarations (RoHS, REACH, UL), request the manufacturer's compliance package with your RFQ.