Siemens 5SJ4125-7HG41 — 1-Pole MCB (DIN Rail)

Siemens SENTRON 5SJ4125-7HG41 MCB, 1-pole, 25 A, C-curve, 10

MPN5SJ4125-7HG41
Active

Siemens SENTRON 5SJ4 series miniature circuit breaker, 5SJ4125-7HG41, 1-pole, 25 A rated current, C tripping characteristic, 10 kA breaking capacity per EN 60898, 1 MW width.

$91.69Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SJ4125-7HG41 — Identification
ParameterValue
Product designationMiniature circuit breakers
Brand nameSENTRON
Number of poles1
Application suitabilityMechanical engineering / industry
5SJ4125-7HG41 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Rated value (EN 60898)10 kA
Overvoltage category3
5SJ4125-7HG41 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodon standard mounting rail
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height110 mm
Depth70 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SJ4125-7HG41 — Environmental
ParameterValue
IP protection classIP20, with connected conductors, IP 40 in the handle range
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens SENTRON 5SJ4125-7HG41 is a 1-pole miniature circuit breaker rated 25 A at AC with a C tripping characteristic, per the datasheet. Rated current holds at 25 A up to 40 °C ambient; above that it derates linearly to 22 A at 60 °C. Pollution degree 3 and overvoltage category 3 mean it's rated for the industrial environment — conductive pollution and transient overvoltages up to 4 kV are within spec.

Mounting and fit

IP20 with connected conductors, IP40 in the handle area — fine for enclosed panels; not rated for washdown. Sealable, halogen-free, silicon-free — relevant for clean-room or corrosive-environment installs where outgassing matters.

Frequently asked questions

What is the breaking capacity of this MCB?

10 kA per EN 60898, which is the standard for miniature circuit breakers in residential and light commercial distribution boards.

What is the C-curve and what loads is it for?

C characteristic trips at 5 to 10 times rated current, making it suitable for circuits with moderate inrush — motor starters, lighting panels, general-purpose branch circuits.

What is the width and mounting?

18 mm (1 modular unit), snaps onto standard 35 mm DIN rail. Mounting position is any.

Does it have tunnel terminals?

No. Combined (box-type) terminals top and bottom. Torque spec is 3.5 Nm for Cu conductors.