Siemens 5SJ4130-7HG40 — 1-Pole MCB (DIN Rail)

Siemens 5SJ4130-7HG40 SENTRON MCB, 1P C-curve, 10 kA

MPN5SJ4130-7HG40
Active

Siemens SENTRON 5SJ4 miniature circuit breaker, 1-pole, C tripping characteristic, 10 kA (EN 60898) / 15 kA (IEC 60947-2), 400 V AC / 60 V DC, 1 MW, IP20, DIN-rail mount.

$30.48 – $80.20Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SJ4130-7HG40 — Identification
ParameterValue
Product designationMiniature circuit breakers
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SJ4130-7HG40 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Overvoltage category3
5SJ4130-7HG40 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodon standard mounting rail
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth70 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SJ4130-7HG40 — Environmental
ParameterValue
IP protection classIP20, with connected conductors, IP 40 in the handle range
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The higher IEC figure gives the buyer headroom when the part is specified into an industrial SCCR study — the 15 kA value is the one that governs coordination in a panel with upstream fuses or a moulded-case breaker. Voltage rating is 400 V AC and 60 V DC, with an insulation voltage (Ui) of 440 V AC. The 60 V DC limit means this pole is not suitable for common 110 V DC control circuits; for DC applications above 60 V you would step to a 2-pole series connection or a different MCB family.

Depth is 70 mm, matching the 5SJ4 family footprint — it drops into existing 5SJ4 panel layouts without rewiring or busbar repositioning.

Neutral conductor is not switched (1-pole only), so this breaker protects the phase leg only; the neutral bar in the panel must be continuous.

Frequently asked questions

What is the breaking capacity and which standard applies?

10 kA per EN 60898 (household/residential standard) and 15 kA per IEC 60947-2 (industrial standard). For a panel SCCR calculation, the 15 kA IEC value is the one to use.

What is the physical size and mounting?

Width 18 mm (1 MW), depth 70 mm, height 90 mm. It snaps onto standard DIN rail and can be mounted in any orientation.

Does it replace the 5SL6006-7 in an existing panel?

The 5SL6006-7 is a different Siemens MCB series (5SL) with a different footprint and terminal layout. The 5SJ4130-7HG40 will not drop into a panel wired for the 5SL series without busbar and wiring changes — it is not a form-fit-function substitute.