It carries a 10 kA breaking capacity per EN 60898 and 15 kA per IEC 60947-2, with a maximum DC rating of 60 V. This is the part you spec into a distribution board or sub-panel for branch circuit protection on motor control or general loads — the C-curve handles inrush from small motors and transformers without nuisance trips.
Fit and ratings
Mount in any position — no derating for orientation. IP20 with conductors connected, IP40 in the handle area — fine for enclosed panels, not for washdown zones. The 60 V DC maximum limits DC use to control circuits or small battery-backed loads, not main DC bus protection.
Deployment context
Rated for mechanical engineering and industry environments per the manufacturer. Vibration resistance of 50 m/s² at 25–150 Hz and 60 m/s² at 35 Hz means it holds up on machine-mounted panels near pumps or compressors.