Skip to main content
Siemens 5SJ4135-8HG41 — 1-Pole MCB (DIN Rail)

Siemens 5SJ4135-8HG41 SENTRON MCB, 1P D 35A, 70mm depth

MPN5SJ4135-8HG41
Active

Siemens SENTRON 5SJ4 series, miniature circuit breaker, 1-pole, D tripping characteristic, 35 A rated at 30-40 °C, AC/DC, depth 70 mm, width 18 mm, height 110 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SJ4135-8HG41 — Identification
ParameterValue
Product designationMiniature circuit breakers
Brand nameSENTRON
Number of poles1
Application suitabilityMechanical engineering / industry
5SJ4135-8HG41 — Electrical & Protection
ParameterValue
Tripping characteristic classD
Rated value (EN 60898)10 kA
Overvoltage category3
5SJ4135-8HG41 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodon standard mounting rail
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height110 mm
Depth70 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SJ4135-8HG41 — Environmental
ParameterValue
IP protection classIP20, with connected conductors, IP 40 in the handle range
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SJ4135-8HG41 is a 1-pole SENTRON miniature circuit breaker with a D tripping characteristic, rated 35 A at both 30 °C and 40 °C ambient. It accepts AC or DC supply up to 60 V DC maximum.

Derating is published: at 45 °C the rating drops to 34 A, at 50 °C to 32.9 A, at 55 °C to 31.8 A, and at 60 °C to 30.8 A (–). Overvoltage category 3, pollution degree 3. Vibration resistance tested to 50 m/s² at 25–150 Hz and 60 m/s² at 35 Hz (4 sec). Suitability for mechanical engineering and industry.

Frequently asked questions

Where can I buy 5SJ4135-8HG41 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is 5SJ4135-8HG41's listed depth?

The depth is 70 mm. Combined with 18 mm width and 110 mm height, it fits standard DIN-rail enclosures.

Will 5SJ4135-8HG41 drop into a panel specified around 5SL6132-6MB without rewiring?

Both are 1-pole MCBs on DIN rail, but the 5SL6132-6MB is a B-curve 32 A device; the 5SJ4135-8HG41 is a D-curve 35 A. The footprint (18 mm width) and terminal type (combined tunnel) are the same, so mechanical fit is identical, but the trip characteristic and rating differ — verify the circuit's inrush and continuous load before substitution.

MPN
5SJ4135-8HG41