It carries a C tripping characteristic, meaning it tolerates moderate inrush currents typical of motor starters and small transformers before opening on overload. Rated breaking capacity is 10 kA per EN 60898 and 15 kA per IEC 60947-2 at 400 V AC — enough for most secondary distribution panels where the upstream transformer limits fault current below those levels. The DC rating stops at 60 V, so it is not a candidate for higher-voltage DC bus protection.
Depth of 70 mm and height of 121 mm fit standard 1-pole MCB cutouts. No tunnel terminals are offered, so the combined style is the only termination option. IP20 with connected conductors, IP40 in the handle area — sufficient for enclosed panel use.