Those aren't interchangeable — EN 60898 is the domestic/commercial standard, IEC 60947-2 is the industrial standard. If your panel SCCR requirement sits at 10 kA or below, the EN rating covers it; above that, you need the IEC rating, which gives you 15 kA headroom.
Pollution degree 3, overvoltage category 3 — that's the standard for fixed industrial installations. Vibration resistance tested to 50 m/s² at 25–150 Hz and 60 m/s² at 35 Hz (4 s).