Siemens 5SJ4163-8HG41 — 1-Pole MCB (DIN Rail)

Siemens 5SJ4163-8HG41 SENTRON MCB, 1P D 63 A 10 kA

MPN5SJ4163-8HG41
Active

Siemens SENTRON 5SJ4 series, miniature circuit breaker, 1-pole, D-curve, 63 A rated at 40 °C, 10 kA breaking capacity per EN 60898, 1 modular width (18 mm).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SJ4163-8HG41 — Identification
ParameterValue
Product designationMiniature circuit breakers
Brand nameSENTRON
Number of poles1
Application suitabilityMechanical engineering / industry
5SJ4163-8HG41 — Electrical & Protection
ParameterValue
Tripping characteristic classD
Rated value (EN 60898)10 kA
Overvoltage category3
5SJ4163-8HG41 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodon standard mounting rail
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height110 mm
Depth70 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SJ4163-8HG41 — Environmental
ParameterValue
IP protection classIP20, with connected conductors, IP 40 in the handle range
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SJ4163-8HG41 is a SENTRON 5SJ4 miniature circuit breaker — 1-pole, D-curve, rated 63 A at AC 40 °C, with a 10 kA breaking capacity per EN 60898. At 63 A continuous, it suits branch circuits feeding a group of small motors or a heavy inductive load.

Derating and thermal limits

Rated 63 A at both 30 °C and 40 °C ambient. Derating starts at 45 °C: 61.1 A, then 59.9 A at 50 °C, 58.3 A at 55 °C, and 56.7 A at 60 °C.

Frequently asked questions

Where can I buy 5SJ4163-8HG41?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Will 5SJ4163-8HG41 drop into a panel that was specified around 5SY7140-8CC without rewiring?

Both are 1-pole, 1-MW DIN-rail MCBs, so the mechanical footprint is identical. The 5SJ4163-8HG41 is a D-curve 63 A; the 5SY7140-8CC is a different curve and rating — verify the trip characteristic and ampacity match your circuit before substitution. No wiring change needed for the busbar or load connections.

What is the depth of the 5SJ4163-8HG41?

70 mm from the DIN-rail mounting face to the front of the housing.