Skip to main content
Siemens 5SJ4201-8HG41 — 2-Pole MCB (DIN Rail)

Siemens 5SJ4201-8HG41 SENTRON MCB, 2P D-Curve, 10kA EN

MPN5SJ4201-8HG41
Active

Siemens SENTRON 5SJ4 series, miniature circuit breaker, 2-pole, D tripping characteristic, 10 kA (EN 60898) / 15 kA (IEC 60947-2), 400 V AC, 60 V DC, width 36 mm, depth 70 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SJ4201-8HG41 — Identification
ParameterValue
Product designationMiniature circuit breakers
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SJ4201-8HG41 — Electrical
ParameterValue
Number of poles2
5SJ4201-8HG41 — Protection
ParameterValue
Tripping characteristic classD
Overvoltage category3
5SJ4201-8HG41 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height110 mm
Depth70 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors, IP 40 in the handle range
5SJ4201-8HG41 — Environmental
ParameterValue
Pollution degree3
5SJ4201-8HG41 — Specifications
ParameterValue
At AC rated value400 V
According to EN 60898 rated value10 kA

Product details

D-curve trip and breaking capacity — what they mean for the panel

The D curve holds through 10–20× rated current for a short interval, then clears on the thermal-magnetic mechanism. Breaking capacity is rated at 10 kA per EN 60898 and 15 kA per IEC 60947-2; the higher IEC figure applies when the breaker is used in industrial distribution per 60947-2, giving the panel designer headroom for higher available fault current at the service entrance.

Halogen-free and silicon-free construction. Vibration resistance: 50 m/s² at 25–150 Hz and 60 m/s² at 35 Hz (4 s). Suitability for operation listed as mechanical engineering / industry. Supply frequency 50 Hz. Insulation voltage (Ui) at AC rated value 440 V.

Frequently asked questions

What is the breaking capacity of 5SJ4201-8HG41?

10 kA per EN 60898 and 15 kA per IEC 60947-2. The higher IEC figure applies when the breaker is applied per 60947-2 in industrial distribution.

What tripping curve does this MCB use?

D characteristic — designed for loads with high inrush current such as motor starters, small transformers, and solenoid banks.

Where can I buy 5SJ4201-8HG41?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

MPN
5SJ4201-8HG41