It is rated 10 kA breaking capacity per EN 60898 and 15 kA per IEC 60947-2 at 400 V AC, with a DC rating of 60 V. The 70 mm depth is a standard panel depth; no special enclosure clearance needed.
Ratings and their meaning for the buyer
The 15 kA rating under IEC 60947-2 gives headroom for industrial distribution boards with higher fault levels — the higher standard certifies the breaker for use as a branch-circuit protective device in motor starter combinations. The D-curve trips magnetically between 10× and 20× In, so it holds through motor starting current without nuisance trips. Overvoltage category 3 and pollution degree 3 mean it is rated for fixed-installation distribution panels, not plug-in portable equipment.