Skip to main content
Siemens 5SJ4211-7HG41 — 2-Pole MCB (DIN Rail)

Siemens 5SJ4211-7HG41 SENTRON MCB, 2P C-Curve, 10kA

MPN5SJ4211-7HG41
Active

Siemens SENTRON 5SJ4 series, 5SJ4211-7HG41, 2-pole miniature circuit breaker, C characteristic, 10 kA interrupting capacity per EN 60898, 15 kA per IEC 60947-2, 400 V AC / 60 V DC, 36 mm width.

$91.44Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SJ4211-7HG41 — Identification
ParameterValue
Product designationMiniature circuit breakers
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SJ4211-7HG41 — Electrical
ParameterValue
Number of poles2
5SJ4211-7HG41 — Protection
ParameterValue
Tripping characteristic classC
Overvoltage category3
5SJ4211-7HG41 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height110 mm
Depth70 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors, IP 40 in the handle range
5SJ4211-7HG41 — Environmental
ParameterValue
Pollution degree3
5SJ4211-7HG41 — Specifications
ParameterValue
At AC rated value400 V
According to EN 60898 rated value10 kA

Product details

Panel fit and interrupting capacity

The Siemens 5SJ4211-7HG41 is a 2-pole C-curve miniature circuit breaker from the SENTRON 5SJ4 family, sized at 2 modular width units (36 mm) for standard DIN-rail mounting. Its C characteristic handles moderate inrush from motor and lighting loads without nuisance tripping, while the 10 kA breaking capacity per EN 60898 covers most commercial and light industrial panelboards. The higher 15 kA rating per IEC 60947-2 applies when the breaker is installed in an industrial distribution board with higher prospective fault current — that's the number to check against your available fault current study. Rated for 400 V AC and 60 V DC circuits, with an insulation voltage (Ui) of 440 V AC. Pollution degree 3 and overvoltage category 3 mean it's rated for the conductive-dust and transient environment typical of control panels near production machinery.

Mounting and wiring details

Sealable design allows the installer to lock the handle position with a padlock for lockout/tagout. IP20 with connected conductors; IP40 in the handle range. Halogen-free and silicon-free construction — relevant for clean-room or semiconductor-adjacent installs where outgassing contaminates processes.

Environmental and compliance

Rated for ambient temperatures from -40 °C to 75 °C, with max 95% humidity. Vibration resistance tested at 50 m/s² over 25 to 150 Hz and 60 m/s² at 35 Hz for 4 seconds — sufficient for machine-mounted panels on pumps or compressors. Suitability for operation listed as mechanical engineering / industry.

Frequently asked questions

What is the interrupting capacity of 5SJ4211-7HG41?

10 kA per EN 60898 for standard household/commercial use, and 15 kA per IEC 60947-2 for industrial distribution boards. Use the 15 kA figure when the available fault current exceeds 10 kA.

Where can I buy 5SJ4211-7HG41?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

MPN
5SJ4211-7HG41